2023-01-17 11:17:33PLUMBING PLAN AUDIT
 PERMIT- 22100869
 1/17/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 AUDIT RESULTS.
  
 1) ARCH. (A) & PLUMB. (P) SHEETS: PLEASE LABEL THE
 TOILET ROOMS AS EITHER MALE AND FEMALE OR UNISEX IN
 ACCORDANCE WITH SECS. 403.2 & 403.2.1 FBC P. PLEASE
 NOTE SEC. 403.3 REQUIRES THAT TOILET FACILITIES BE
 PROVIDED FOR BOTH THE PUBLIC AND EMPLOYEES. THE VIP
 BATHROOM DESIGNATION APPEARS TO IMPLY EXCLUSIVE USE
 WHICH IS NON-COMPLIANT.
  
 2) ARCH. (A) & PLUMB. (P) SHEETS: THE DRINKING
 FOUNTAINS HAVE LEADING EDGES THAT ARE PROTRUDING INTO
 THE CIRCULATION PATH BEYOND THE MAXIMUM 4-INCHES
 ALLOWABLE- SEC. 307.2 FBC ACC.
  
 3) A8.00- FBC ACC DEFICIENCIES:
 A) DETAILS 1 & 6: SHOW THE DIMENSIONS OF THE WATER
 CLOSET CLEAR SPACES, AND THE CLEAR FLOOR SPACE DIAGRAM
 AND DIMENSIONS FOR THE LAVATORIES- SECS. 604.3 & 606.2.
 B) DETAIL 6: SHOW THE DIAMETER OF THE TURNING CIRCLE-
 SEC. 304.3.
 C) DETAILS 1, 5, 6, & 8: SHOW THE CENTERLINES OF THE
 WATER CLOSET DRAINS MEASURED FROM THE ADJACENT WALLS-
 604.2.
 D) DETAILS 1, 2, 6, & 9: THE MINIMUM WATER CLOSET GRAB
 LENGTHS AND MAX SPACING FROM THE SIDE WALLS ARE NOT
 DETAILED IN COMPLIANCE WITH SEC. & FIGURE 604.5.1.
 E) PROVIDE THE CLEAR FLOOR SPACE DIAGRAMS AND
 DIMENSIONS FOR THE BREAK ROOM AND EXAM ROOM SINKS-
 SECS. 212.3 & 606.2.
 F) PROVIDE THE HEIGHTS OF THE BREAK ROOM AND EXAM SINK
 RIMS OR COUNTER SURFACES FROM THE FINISHED FLOOR- SEC.
 212,3 & 606.3.
  
 4) SHEETS P0.1 & P2.1: THE ISOMETRIC DRAWINGS SHOW
 SKS-1, 2, & 3 WHICH ARE NOT INCLUDED IN THE FIXTURE
 SCHEDULE- SEC. 107.2.1 WPB.
  
 5) P2.1: PROVIDE VENTS FOR THE SK-2 SINKS LOCATED IN
 THE LASER ROOM, AND BY THE BIO-HAZARD CLOSET- SEC.
 902.2.1 FBC P. PLEASE NOTE THE SINKS CANNOT BE VENTED
 USING THE THE HORIZONTAL WET VENT FOR THE BATHROOM-
 SEC. 912.1.
  
 6) P2.1: INDICATE HOW TEMPERED WATER WILL BE DELIVERED
 FROM THE LAVATORY SINKS- SEC. 419.5 & 607.1.2 FBC P.
  
 7) P3.1: A MEANS OF LIMITING THE HOT WATER TEMPERATURE
 AT THE WATER HEATER IS REQUIRED PER SEC. 607.1.1 FBC P.
 PLEASE PROVIDE A MASTER THERMOSTATIC MIXING VALVE AND
 SHOW THE LOCATION IN THE WATER HEATER PIPING DETAIL.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  