Plan Review Notes
Plan Review Notes For Permit 22100869
Permit Number 22100869
Review Stop M
Sequence Number 1
Notes
Date Text
2023-01-16 09:45:041ST REVIEW FMC
 PERMIT: 22100869
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-1.1: EF-2 IS LOCATED IN THE BIO-HAZARD
 STORAGE AREA; SHEET M-0.1 INDICATES EF-2 AREA SERVED IS
 JANITOR CLOSET AND IS CONTROLLED BY AN OCCUPANCY
 SENSOR. PLEASE EXPLAIN WHY THE DIFFERENCES ON THE 2
 SHEETS? WHAT EXACTLY IS TO BE STORED IN THE BIO HAZARD
 AREA? SHOULD THE EXHAUST FAN BE CONTINUOUSLY OPERATED?
 FBC 107.3.5
  
 2) SHOW ON THE SITE PLAN THAT THE OUTDOOR AIR
 TERMINATIONS MEET THE 10 FEET FROM LOT LINES.
 FMC 401.4
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  