2022-10-26 14:07:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| 1) SHEET CS - THERE IS AN INDICATION UNDER APPLICABLE |
| CODES OF THE 6TH ED OF NFPA 101. |
| |
| THE CURRENT EDITION OF NFPA 101 ADOPTED BY THE STATE OF |
| FLORIDA IS THE 7TH ED. |
| |
| PLEASE REVIEW, ENSURE COMPLIANCE AND CORRECT. |
| |
| |
| |
| 1A) SHEET CS - THERE IS AN INDICATION UNDER APPLICABLE |
| CODES OF THE NFPA 101, OF CHAPTER 42. |
| |
| THE CLASSIFICATION OF BUSINESS OCCUPANCY WITHIN NFPA |
| 101 IS CHAPTER 38 |
| |
| PLEASE REVIEW, ENSURE COMPLIANCE AND CORRECT. |
| |
| |
| 2) SHEET CS - THERE IS AN INDICATION UNDERNOTES OF |
| INTERIOR FINISHES COMPLYING WITH LIFE SAFETY 101 2015 |
| ED. |
| |
| THE CURRENT EDITION OF NFPA 101 ADOPTED BY THE STATE OF |
| FLORIDA IS THE 2020 ED.. |
| |
| PLEASE REVIEW, ENSURE COMPLIANCE AND CORRECT |
| |
| |
| |
| 3) SHEET A2.00 - THERE IS AN INDICATION UNDER FLOOR |
| NOTES # 8 OF - SEE ROOM FINISH SCHEDULES FOR ....FLOOR |
| COVERINGS. |
| |
| THE FLOOR COVERINGS COULD NOT BE LOCATED. |
| |
| PER NFPA 101 CH 30 |
| |
| 30.3.3.3 INTERIOR FLOOR FINISH. |
| 30.3.3.3.1 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| SECTION 10.2. |
| 30.3.3.3.2 INTERIOR FLOOR FINISH IN EXIT ENCLOSURES AND |
| EXIT ACCESS COR RIDORS AND SPACES NOT SEPARATED FROM |
| THEM BY WALLS COMPLYING WITH |
| 30.3.6 SHALL BE NOT LESS THAN CLASS II. |
| 30.3.3.3.3 INTERIOR FLOOR FINISH SHALL COMPLY WITH |
| 10.2.7.1 OR 10.2.7.2, |
| AS APPLICABLE |
| |
| PLEASE REVIEW, ENSURE COMPLIANCE, CORRECT AND PROVIDE A |
| NOTE OF ACKNOWLEDGMENT. |
| |
| |
| 4) SHEET A2.01 - WITHIN THE LIFE SAFETY DEVICE SYMBOL |
| LIST THERE ARE INDICATIONS OF FIRE ALARM DEVICES. |
| |
| THOUGH THERE ARE NO SYMBOLS WITHIN THE FLOOR PLAN, |
| PLEASE CLARIFY IF A FIRE ALARM WILL OR WILL NOT BE |
| INSTALLED. |
| |
| SHOULD A FIRE ALARM BE INSTALLED IT SHALL BE INSTALLED |
| UNDER A SEPARATE PERMIT AND SHOP DRAWINGS. |
| |
| IF SO, PLEASE PROVIDE A NOTE OF ACKNOWLEDGMENT OF THIS |
| PLAN SHEET AND THE ELECTCAL PLAN SHEET. |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |