Plan Review Notes For Permit 22100849
Permit Number 22100849
Review Stop B
Sequence Number 2
Notes
Date Text
2022-12-20 15:18:31BUILDING PROVISO:
 2020 FBC-B 1210.2.2. WALLS & PARTITIONS. THIS COMMENT
 IS A RESULT OF THE BUILDING OFFICIAL INTERPRETATION ON
 06/2020. IN BATHROOMS, RESTROOMS & SERVICE SINK AREAS
 EPOXY PAINT IS NO LONGER CONSIDERED A SMOOTH HARD,
 NON-ABSORBENT SURFACE.
 2020 FBC-B 2509.2 BASE FOR TILE. MATERIALS USED AS A
 BASE FOR WALL TILE IN TUB AND SHOWER AREAS AND WALLS
 AND CEILING PANELS IN SHOWER AREAS SHALL BE OF
 MATERIALS LISTED IN TABLE 2509.2 AND INSTALLED IN
 ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. WATER
 RESISTANT GYPSUM (MR BOARD) SHALL NOT BE USED FOR
 SHOWER & TUB ENCLOSURES BUT CAN BE USED FOR BACKING
 BOARD FOR A BASE FOR TILE IN WATER CLOSET COMPARTMENT
 WALLS WHEN INSTALLED IN ACCORDANCE WITH GA-216 OR ASTM
 C840 AND THE MANUFACTURE'S RECOMMENDATIONS.
 JAMES A. WITMER BN, PX, SFP, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
  