Plan Review Notes
Plan Review Notes For Permit 22100849
Permit Number 22100849
Review Stop M
Sequence Number 1
Notes
Date Text
2022-11-17 16:13:571ST REVIEW FMC
 PERMIT: 22100849
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
  
 1) PROVIDE A DETAIL DRAWING OF THE DRYER EXHAUST DUCT
 AND HOW IT WILL REMAIN OUT OF THE RATED FLOOR/CEILING
 ASSEMBLY. FBC 107.3.5
  
 2) SHOW THAT THE DRYER DUCT EXHAUST TERMINATION
 LOCATION IS A MINIMUM 3 FEET FROM ANY OPERABLE OPENINGS
 INTO THE BUILDING. FMC 501.3.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  