Plan Review Notes For Permit 22100849 |
Permit Number |
22100849 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-12-01 10:49:04 | ELECTRIC REVIEW FAILED | | 1) COVER SHEET INDICATES ELECTRIC PANELS TO BE CHANGED | | TO 100-AMP FROM 60-AMP. APARTMENT LOAD CALCULATIONS | | INDICATE LOADS OF 81 AND 82 AMPS FOR ONE BEDROOM AND | | STUDIO APARTMENTS. PLEASE PROVIDE A BUILDING RISER | | DIAGRAM INDICATING ALL EQUIPMENT, CONDUCTOR AND | | OVERCURRENT PROTECTION SIZES. NEC 215.5 | | 2) PLEASE PROVIDE AN ENTIRE BUILDING ELECTRIC LOAD | | CALCULATION. NEC 230.23 (A) | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. | | | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2020 7TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2020 7TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 | | 7TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 | | 7TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION | | NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | | | MICHAEL PETERSON | | ELECTRICAL PLANS EXAMINER | | [email protected] | | 561-805-6746 | | |
|