2023-02-03 10:31:11 | ELECTRIC REVIEW FAILED |
| |
| ELECTRIC REVIEW COMMENTS |
| |
| 1) METER IS DESCRIBED AS UTILITY SERVICE WITH UTILITY |
| DISCONNECT. IS THIS A METER MAIN OR METER WITH SEPARATE |
| DISCONNECTS FOR EXISTING PANELS A AND B. ORIGINAL HOUSE |
| PLANS DETAIL A RISER DIAGRAM WITH METER, 2 DISCONNECTS |
| AND 2, 150-AMP, MLO PANELS? PLEASE PROVIDE AN ACCURATE |
| ELECTRIC RISER DIAGRAM, ONE DETAILING EXISTING |
| CONDITIONS AND ONE DETAILING PROPOSED CHANGES. ALSO |
| PROVIDE LOAD CALCULATIONS FOR THE ENTIRE SERVICE AND |
| EACH INDIVIDUAL LOAD CENTER, AND, ALL PANEL SCHEDULES. |
| |
| 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY |
| HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS |
| SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF THE |
| FEEDERS. SUCH A DIAGRAM SHALL SHOW THE AREA IN SQUARE |
| FEET OF THE BUILDING OR OTHER STRUCTURE SUPPLIED BY |
| EACH FEEDER, THE TOTAL CALCULATED LOAD BEFORE APPLYING |
| DEMAND FACTORS, THE DEMAND FACTORS USED, THE CALCULATED |
| LOAD AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND |
| TYPE OF CONDUCTORS TO BE USED. |
| |
| 2) EXISTING PANEL B IS DETAILED AS MAIN LUG ONLY AND |
| MAIN BREAKER. PLEASE REMOVE ANY CONFLICTS IN EQUIPMENT |
| DESCRIPTION. |
| |
| FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF |
| THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT |
| LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED |
| BY THE BUILDING OFFICIAL |
| |
| 3) A DISCONNECTING MEANS MUST BE PROVIDED FOR PANEL B |
| AND GROUPED WITH ALL OTHER DISCONNECTING MEANS |
| |
| 230.72 GROUPING OF DISCONNECTS. (A) GENERAL. THE TWO TO |
| SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE |
| GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE |
| THE LOAD SERVED. |
| |
| |
| 4) DO NOT USE INCORRECT NOMENCLATURE IN THIS SUBMITTAL. |
| IE, THE ELECTRICAL DATA SPECS, LABELS INDICATE TO BE |
| PLACED AT MAIN SERVICE PANEL. NO EQUIPMENT ON ANY |
| DIAGRAM INDICATES A MAIN SERVICE PANEL. FBC 107.3 |
| |
| 5) THE GARAGE FLOOR PLAN DETAILS 3 LOAD CENTERS |
| DESCRIBED AS NLC-B, N-LC AND BULC. THE ONE LINE DIAGRAM |
| DETAILS 2 LOAD CENTERS DESCRIBED AS LOAD CENTER BACKUP |
| AND EXISTING DISTRIBUTION PANEL A. THE ONE LINE DIAGRAM |
| DETAILS BOTH OF THESE PANELS ARE LOCATED NEAR HUB. ONCE |
| AGAIN IT APPEARS THE NOMENCLATURE USED ON BOTH THE |
| GARAGE FLOOR PLAN AND ONE LINE DIAGRAM DO NOT MATCH. |
| PLEASE CLEARLY IDENTIFY ALL EQUIPMENT CORRECTLY ON ALL |
| PLANS. FBC 107.2 |
| |
| |
| 6) PROVIDE A LEGEND ON ALL PLANS IDENTIFYING ALL |
| ACRONYMS OR SYMBOLS. IE, DOES BULC MEAN BACK UP LOAD |
| CENTER? FBC 107.2 |
| |
| 7) INCLUDE SPECIFIC LABELS ON, THE ELECTRICAL DATA |
| SPECS/ LABELS SHEET, FOR ALL EQUIPMENT TO COMPLY WITH |
| NEC 408.4 FIELD IDENTIFICATION REQUIRED. (A) CIRCUIT |
| DIRECTORY OR CIRCUIT IDENTIFICATION. (B) SOURCE OF |
| SUPPLY. |
| |
| 8) REMOVE NOTE STATING INSTALL CREW IS TO VERIFY WIRE |
| SIZE TO DISTRIBUTION PANEL B. ALL PLANS REQUIRE WIRE, |
| EQUIPMENT, OVERCURRENT PROTECTION, ETC, TO BE INCLUDED |
| IN PLANS SUBMITTED FOR ELECTRICAL PLAN REVIEW.FBC 107.2 |
| AND NEC 215.5 |
| |
| |
| 9) IT APPEARS MANY OF THE TRIANGLE NOTATIONS ON THE ONE |
| LINE DIAGRAM ARE INCORRECT. PLEASE PROVIDE CLEAR AND |
| ACCURATE NOTATIONS ON ALL PLANS. FBC 107.2 |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |
| V/R, |
| |