2023-02-03 10:31:11ELECTRIC REVIEW FAILED
  
 ELECTRIC REVIEW COMMENTS
  
 1) METER IS DESCRIBED AS UTILITY SERVICE WITH UTILITY
 DISCONNECT. IS THIS A METER MAIN OR METER WITH SEPARATE
 DISCONNECTS FOR EXISTING PANELS A AND B. ORIGINAL HOUSE
 PLANS DETAIL A RISER DIAGRAM WITH METER, 2 DISCONNECTS
 AND 2, 150-AMP, MLO PANELS? PLEASE PROVIDE AN ACCURATE
 ELECTRIC RISER DIAGRAM, ONE DETAILING EXISTING
 CONDITIONS AND ONE DETAILING PROPOSED CHANGES. ALSO
 PROVIDE LOAD CALCULATIONS FOR THE ENTIRE SERVICE AND
 EACH INDIVIDUAL LOAD CENTER, AND, ALL PANEL SCHEDULES.
  
 215.5 DIAGRAMS OF FEEDERS. IF REQUIRED BY THE AUTHORITY
 HAVING JURISDICTION, A DIAGRAM SHOWING FEEDER DETAILS
 SHALL BE PROVIDED PRIOR TO THE INSTALLATION OF THE
 FEEDERS. SUCH A DIAGRAM SHALL SHOW THE AREA IN SQUARE
 FEET OF THE BUILDING OR OTHER STRUCTURE SUPPLIED BY
 EACH FEEDER, THE TOTAL CALCULATED LOAD BEFORE APPLYING
 DEMAND FACTORS, THE DEMAND FACTORS USED, THE CALCULATED
 LOAD AFTER APPLYING DEMAND FACTORS, AND THE SIZE AND
 TYPE OF CONDUCTORS TO BE USED.
  
 2) EXISTING PANEL B IS DETAILED AS MAIN LUG ONLY AND
 MAIN BREAKER. PLEASE REMOVE ANY CONFLICTS IN EQUIPMENT
 DESCRIPTION.
  
 FBC 107.2 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL
  
 3) A DISCONNECTING MEANS MUST BE PROVIDED FOR PANEL B
 AND GROUPED WITH ALL OTHER DISCONNECTING MEANS
  
 230.72 GROUPING OF DISCONNECTS. (A) GENERAL. THE TWO TO
 SIX DISCONNECTS AS PERMITTED IN 230.71 SHALL BE
 GROUPED. EACH DISCONNECT SHALL BE MARKED TO INDICATE
 THE LOAD SERVED.
  
  
 4) DO NOT USE INCORRECT NOMENCLATURE IN THIS SUBMITTAL.
 IE, THE ELECTRICAL DATA SPECS, LABELS INDICATE TO BE
 PLACED AT MAIN SERVICE PANEL. NO EQUIPMENT ON ANY
 DIAGRAM INDICATES A MAIN SERVICE PANEL. FBC 107.3
  
 5) THE GARAGE FLOOR PLAN DETAILS 3 LOAD CENTERS
 DESCRIBED AS NLC-B, N-LC AND BULC. THE ONE LINE DIAGRAM
 DETAILS 2 LOAD CENTERS DESCRIBED AS LOAD CENTER BACKUP
 AND EXISTING DISTRIBUTION PANEL A. THE ONE LINE DIAGRAM
 DETAILS BOTH OF THESE PANELS ARE LOCATED NEAR HUB. ONCE
 AGAIN IT APPEARS THE NOMENCLATURE USED ON BOTH THE
 GARAGE FLOOR PLAN AND ONE LINE DIAGRAM DO NOT MATCH.
 PLEASE CLEARLY IDENTIFY ALL EQUIPMENT CORRECTLY ON ALL
 PLANS. FBC 107.2
  
  
 6) PROVIDE A LEGEND ON ALL PLANS IDENTIFYING ALL
 ACRONYMS OR SYMBOLS. IE, DOES BULC MEAN BACK UP LOAD
 CENTER? FBC 107.2
  
 7) INCLUDE SPECIFIC LABELS ON, THE ELECTRICAL DATA
 SPECS/ LABELS SHEET, FOR ALL EQUIPMENT TO COMPLY WITH
 NEC 408.4 FIELD IDENTIFICATION REQUIRED. (A) CIRCUIT
 DIRECTORY OR CIRCUIT IDENTIFICATION. (B) SOURCE OF
 SUPPLY.
  
 8) REMOVE NOTE STATING INSTALL CREW IS TO VERIFY WIRE
 SIZE TO DISTRIBUTION PANEL B. ALL PLANS REQUIRE WIRE,
 EQUIPMENT, OVERCURRENT PROTECTION, ETC, TO BE INCLUDED
 IN PLANS SUBMITTED FOR ELECTRICAL PLAN REVIEW.FBC 107.2
 AND NEC 215.5
  
  
 9) IT APPEARS MANY OF THE TRIANGLE NOTATIONS ON THE ONE
 LINE DIAGRAM ARE INCORRECT. PLEASE PROVIDE CLEAR AND
 ACCURATE NOTATIONS ON ALL PLANS. FBC 107.2
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  
  