Plan Review Notes
Plan Review Notes For Permit 22100670
Permit Number 22100670
Review Stop G
Sequence Number 1
Notes
Date Text
2022-10-25 14:16:511ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100670
 10/25/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) P1 GAS RISER: TO HELP EXPEDITE THE REVIEW PLEASE
 SHOW THE LENGTHS OF THE BRANCH PIPES AND THE TOTAL
 DEVELOPED LENGTH OF THE PIPING- SEC. G2413.4.1 FBC RES.
  
 2) P1 GAS RISER: BASED ON THE SUBMITTED SPECIFICATIONS
 PLEASE CORRECT THE GAS LOAD OF THE RANGE TO 99,000
 BTU???S- SEC. G2413.2 FBC RES.
  
 3) P1: INDICATE HOW COMBUSTION AIR WILL BE PROVIDED TO
 THE RANGE AND PROVIDE CALCULATIONS- SECTION G2407.1 FBC
 RES.
  
 4) P1: THE 100,000 BTU GAS LOADS FOR THE WATER HEATERS
 SEEM LOW. PLEASE SUBMIT MANUFACTURER???S SPECIFICATIONS
 FOR THE UNITS TO VERIFY GAS LOADS ARE ACCURATE- SEC.
 G2448.1
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER