2022-11-02 09:54:39 | ELECTRIC REVIEW FAILED |
| 1) RISER DIAGRAM DETAILS 2/0 CU CONDUCTORS FEEDING (2) |
| 2OO AMP PANELS IN GARAGE. |
| RISER DIAGRAM DETAILS REDUCED CONDUCTOR AMPACITY. THE |
| REDUCED CONDUCTOR AMPACITY IS ONLY APPLICABLE TO |
| CONDUCTORS SERVING THE ENTIRE LOAD ASSOCIATED WITH A |
| DWELLING. PLEASE CORRECT CONDUCTOR SIZES AS APPLICABLE. |
| NEC 310.15 (B)(7)(2) |
| 2) GYM IS FED BY MULTIPLES CIRCUITS FED FROM ELECTRIC |
| PANEL IN GARAGE. THIS DOES NOT COMPLY WITH 225.30 |
| NUMBER OF SUPPLIES. A BUILDING OR OTHER STRUCTURE THAT |
| IS SERVED BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD |
| SIDE OF A SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED |
| BY ONLY ONE FEEDER OR |
| BRANCH CIRCUIT. PLEASE CORRECT AS APPLICABLE. IF A |
| SEPARATE PANEL IS TO BE INSTALLED AT THE GYM, PLEASE |
| DETAIL IT IN THE RISER DIAGRAM AND THE REQUIRED, |
| ADDITIONAL, GROUNDING ELECTRODE SYSTEM AS PER 250.32 |
| 3) PLEASE CORRECT COMPRESSOR 1 AND 2, CONDUCTOR OR |
| OVERCURRENT PROTECTION SIZES, ON PANEL SCHEDULES, TO |
| COMPLY WITH NEC 240.4 OR 310.15 |
| 4) PLEASE CORRECT BATHROOM GFI, CONDUCTOR, OVERCURRENT |
| PROTECTION SIZE AND CIRCUITRY DETAILS ON PANEL |
| SCHEDULES AND FLOOR PLANS TO COMPLY WITH NEC 210.11 |
| (C)(3) |
| 5) PLEASE DETAIL A NOTE ON ELECTRICAL PLANS AND COVER |
| SHEET, STATING POOL AND GENERATOR WIRING, IF APPLICABLE |
| REQUIRE SEPARATE PERMITS. |
| |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. |
| |
| CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| BUILDING CODE 2020 7TH ED. |
| FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020 |
| 7TH EDITION |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION |
| NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| |