Plan Review Notes
Plan Review Notes For Permit 22100670
Permit Number 22100670
Review Stop E
Sequence Number 1
Notes
Date Text
2022-11-02 09:54:39ELECTRIC REVIEW FAILED
 1) RISER DIAGRAM DETAILS 2/0 CU CONDUCTORS FEEDING (2)
 2OO AMP PANELS IN GARAGE.
 RISER DIAGRAM DETAILS REDUCED CONDUCTOR AMPACITY. THE
 REDUCED CONDUCTOR AMPACITY IS ONLY APPLICABLE TO
 CONDUCTORS SERVING THE ENTIRE LOAD ASSOCIATED WITH A
 DWELLING. PLEASE CORRECT CONDUCTOR SIZES AS APPLICABLE.
 NEC 310.15 (B)(7)(2)
 2) GYM IS FED BY MULTIPLES CIRCUITS FED FROM ELECTRIC
 PANEL IN GARAGE. THIS DOES NOT COMPLY WITH 225.30
 NUMBER OF SUPPLIES. A BUILDING OR OTHER STRUCTURE THAT
 IS SERVED BY A BRANCH CIRCUIT OR FEEDER ON THE LOAD
 SIDE OF A SERVICE DISCONNECTING MEANS SHALL BE SUPPLIED
 BY ONLY ONE FEEDER OR
 BRANCH CIRCUIT. PLEASE CORRECT AS APPLICABLE. IF A
 SEPARATE PANEL IS TO BE INSTALLED AT THE GYM, PLEASE
 DETAIL IT IN THE RISER DIAGRAM AND THE REQUIRED,
 ADDITIONAL, GROUNDING ELECTRODE SYSTEM AS PER 250.32
 3) PLEASE CORRECT COMPRESSOR 1 AND 2, CONDUCTOR OR
 OVERCURRENT PROTECTION SIZES, ON PANEL SCHEDULES, TO
 COMPLY WITH NEC 240.4 OR 310.15
 4) PLEASE CORRECT BATHROOM GFI, CONDUCTOR, OVERCURRENT
 PROTECTION SIZE AND CIRCUITRY DETAILS ON PANEL
 SCHEDULES AND FLOOR PLANS TO COMPLY WITH NEC 210.11
 (C)(3)
 5) PLEASE DETAIL A NOTE ON ELECTRICAL PLANS AND COVER
 SHEET, STATING POOL AND GENERATOR WIRING, IF APPLICABLE
 REQUIRE SEPARATE PERMITS.
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  
 CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2020 7TH ED.
 FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2020
 7TH EDITION
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2020 7TH EDITION
 NEC = NFPA 70 2017 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 MICHAEL PETERSON
 ELECTRICAL PLANS EXAMINER
 [email protected]
 561-805-6746
  