Plan Review Notes
Plan Review Notes For Permit 22100633
Permit Number 22100633
Review Stop E
Sequence Number 2
Notes
Date Text
2023-07-28 15:10:18ELECTRIC REVIEW FAILED
  
 1) PROVIDE AN ELECTRICAL DIAGRAM THAT INCLUDES
 OVERCURRENT PROTECTION SIZES, REFERENCES TO LOCATION OF
 CONDUITS , JUNCTION BOXES, DATUM PLANE HEIGHTS,
 SEAWALLS AND PILINGS, DERATING OF CONDUCTORS, SIGNS,
 AND AND ALL OTHER DETAILS INCLUDING BUT NOT LIMITED TO
 GFP FOR FEEDERS AND OTHER APPLICABLE REQUIREMENTS IN
 ACCORDANCE WITH NEC ARTICLE 555. DRAWING IS VERY
 UNCLEAR. FBC 107.2 , NEC 555
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  