Plan Review Notes For Permit 22100597 |
Permit Number |
22100597 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-12-13 15:25:14 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 22100597 | | 12/13/2022 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE SUBMIT GREASE INTERCEPTOR PLANS IN ACCORDANCE | | WITH SEC. 107.3.5.1.3 WPB. PLEASE INCLUDE THE FOLLOWING | | ITEMS. | | A) EQUIPMENT SCHEDULE INDICATING THE MAKES AND MODELS | | AND CAPACITIES OF THE UNITS. | | B) SIZING CALCULATIONS IN ACCORDANCE WITH ASME | | A112.14.3, ASME A112.14.4, ASME A112.14.6, CSA B481.3, | | OR PDI G101 FOR HYDROMECHANICAL TYPES; OR SEC. 1003.3.7 | | FOR GRAVITY TYPES. | | C) ENLARGED PIPING DIAGRAM INCLUDING LOCATIONS AND | | SIZES OF INLETS, OUTLETS, CLEANOUTS, FLOW CONTROL | | VENTS, AND SAMPLING PORTS. | | D) DIMENSIONED TANK BURIAL, ANCHORING, AND BACKFILLING | | DETAILS. | | E) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION | | GUIDELINES WITH APPROVAL STAMP BY THE ENGINEER OF | | RECORD- SECS.1003.3.5 OR 1003.3.7 FBC P. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|