Plan Review Notes For Permit 22100534 |
Permit Number |
22100534 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-04-04 13:01:05 | 1ST REVIEW FBC-2020 PLUMBING | | PERMIT- 22100534 | | 4/4/2023 | | | | CODES IN EFFECT: | | | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) SHEETS M4.2 & M4.3: PLEASE DETAIL HOW TEMPERED WATER | | WILL BE DELIVERED FROM THE RELOCATED LAVATORY IN | | ACCORDANCE WITH SECS. 419.5 7 607.1.2 FBC P. | | | | 2) M4.2 & M4.3: THE THERMOSTAT CONTROL ON THE NEW WATER | | HEATER CANNOT BE THE LIMITING DEVICE FOR HOT WATER | | DELIVERY TO THE FIXTURES. PLEASE PROVIDE A MASTER | | THERMOSTATIC MIXING DEVICE AT THE WATER HEATER IN ORDER | | TO MEET COMPLIANCE- SEC. 607.1.1 FBC P. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|