Plan Review Notes
Plan Review Notes For Permit 22100496
Permit Number 22100496
Review Stop G
Sequence Number 1
Notes
Date Text
2022-10-25 16:32:301ST REVIEW FBC-2020 FUEL GAS
 PERMIT- 22100496
 10/25/22
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FBC FG- FLORIDA FUEL GAS CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE A BASIC FLOOR OR SITE PLAN SHOWING THE
 LOCATIONS OF ALL THE GAS-FIRED APPLIANCES- SEC. 107.2.1
 WPB. PLEASE NOTE THE APPROVED REMODELING PLANS UNDER
 PERMIT 21100750 DID NOT SHOW THE FIREPLACE, THE GRILL,
 AND ONLY ONE OF THE TWO TANKLESS WATER HEATERS.
  
 2) THE $8500.00 PERMIT VALUE IS LOW BASED ON THE SCOPE
 OF THE PROJECT AND APPLIANCES LISTED ABOVE THAT WERE
 NOT INCLUDED IN THE MASTER. PLEASE NOTE THAT PERMIT
 VALUE IS BASED ON LABOR, MATERIALS, EQUIPMENT AND
 APPLIANCES- SEC. 109.3 WPB.
  
 3) GAS RISER: A SEPARATE PERMIT IS REQUIRED FOR THE
 GENERATOR. PLEASE INDICATE IT AS ???FUTURE GENERATOR???
 ON THE DRAWING AND SHOW A SHUT OFF VALVE AND GAS-TIGHT
 CAP WILL BE INSTALLED AT THE OUTLET- SEC. 107.2.1 WPB
 AND SEC. G2415.15 FBC RES.
  
 4) GAS RISER: TO HELP EXPEDITE THE REVIEW PLEASE
 PROVIDE THE TOTAL DEVELOPED LENGTH OF THE SYSTEM FROM
 THE METER TO THE MOST REMOTE OUTLET- SEC G2413.4.1 FBC
 RES. IT APPEARS TO BE 190 FT.
  
 5) GAS RISER: PROVIDE THE EHD OF THE CSST- TABLE
 402.4(17) FBC FG.
  
 6) GAS RISER: PLEASE NOTE THAT THE SPACE BETWEEN THE
 SLEEVE AND CSST PIPING WILL BE SEALED AT THE ISLAND AND
 THE OPPOSITE END WILL BE VENTED TO THE OUTDOORS- SEC.
 G2415.8.1 FBC RES.
  
 7) GAS FIREPLACE: PLEASE SUBMIT MANUFACTURER???S
 SPECIFICATIONS THAT INCLUDE THE LISTING NUMBER OF THE
 UNIT- SECS. G2435 & G2436 FBC RES.
  
 A) PROVIDE COMBUSTION AIR CALCULATIONS AND INDICATE HOW
 THE AIR WILL BE PROVIDED- SEC. G2407.1 FBC RES.
  
 B) PROVIDE A VENTING DIAGRAM SHOWING THE TYPE AND SIZE
 OF VENT FLUE AND THE TERMINATION LOCATION- SEC. G2427.1
 FBC RES.
  
 8) TANKLESS WATER HEATERS: ON THE FLOOR OR SITE PLAN
 PLEASE SHOW THE CLEARANCES DISTANCES FROM THE WATER
 HEATERS TO OPERABLE OPENINGS AND AIR INTAKES INTO THE
 BUILDING- SECS. G2427.8 & G2448.1 FBC RES.
  
 9) GAS BBQ: ON THE FLOOR OR SITE PLAN PLEASE SHOW THE
 LOCATION OF THE UNIT TO VERIFY IT WILL NOT BE IN AN
 ENCLOSED SPACE WITHOUT INSTALLATION OF A HOOD AND
 EXHAUST SYSTEM- REFER TO THE MANUFACTURER???S
 SPECIFICATIONS AND INSTALLATION GUIDELINES- SEC.
 G2447.1 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  