Plan Review Notes
Plan Review Notes For Permit 22100341
Permit Number 22100341
Review Stop P
Sequence Number 2
Notes
Date Text
2023-01-04 10:15:22PERMIT 22100341- REVISED PLUMBING PLANS DENIED.
 1/4/2023
  
 FAILED COMMENTS FROM THE 1ST REVIEW ARE LISTED BELOW
 WITH ADDITIONAL NOTES FOR FURTHER CLARIFICATION.
  
  
 3) 2ND REQUEST. P-5.2.6: PROVIDE AN RPZ BACKFLOW
 PREVENTER FOR THE WATER LINE TO THE SPA EQUIPMENT- SEC.
 608.17.4.1 FBC P AND SECS. C, D, & E- WPB CROSS
 CONNECTION MANUAL. PLEASE PROVIDE EQUIPMENT SCHEDULES
 FOR BOTH THE SPA AND POOL BF PREVENTERS- SEC. 608.3 FBC
 P.
  
 4) 2ND REQUEST. SUBMIT REVISED SHEETS P-5.2.4 & P-6.2.1
 SHOWING THE DRAINAGE TO BE DECHLORINATED AND DISCHARGED
 TO STORM, OR PLACE A NOTE ON SHEET P-2.2.1 FOR
 CLARIFCATION.
 P-2.2.1: DETAIL P-6 FOR POOL AND SPA BACKWASH DRAINAGE
 IS REFERENCED ON THE PLAN. THE DETAIL IS 11/P-6.2.1
 WHICH WAS NOT PROVIDED BUT REVIEW OF THE MAIN PLUMBING
 PLANS SHOWS THE POOL BACKWASH DRAINING INTO THE
 SANITARY SYSTEM WHICH IS PROHIBITED PER SEC. 90-126 (5)
 WPB.
  
 6) 2ND REQUEST. THE RESPONSE NARRATIVE INDICATES THE
 BRIDGE ROOF DRAINAGE ON NEW SHEET P-2.1.4 WHICH WAS NOT
 UPLOADED FOR REVIEW.
 SHEETS P-2.2.3, P-2.2.5 & P-5.2.5: PLEASE PROVIDE A
 DIMENSIONED BRIDGE ROOF DRAINAGE PLAN THAT SHOWS THE
 LOCATIONS OF THE PRIMARY AND SECONDARY (OVERFLOW) ROOF
 DRAINS, RAINFALL RATE, AND GPM FLOW AT THE RD LOCATION-
 SEC. 1105.1 & 1106.1 FBC P. THE RESPONSE NARRATIVE
 INDICATES A THE ROOF DRAINAGE ON NEW SHEET P-2.1.4
 WHICH WAS NOT UPLOADED FOR REVIEW.
  
 7) 2ND REQUEST. MINIMUM REQUIRED APPLICATIONS FOR THE
 POTABLE WATER BACKFLOW PREVENTER AND GREASE INTERCEPTOR
 NOT PROVIDED. PLEASE NOTE THAT SEPARATE PERMITS ARE
 REQUIRED FOR THE POTABLE WATER BACKFLOW PREVENTER,
 GREASE INTERCEPTOR, IRRIGATION, IRRIGATION BACKFLOW,
 AND POOL. IF REQUESTED GAS CAN ALSO BE UNDER A SEPARATE
 PERMIT. DUE TO A CHANGE IN PROCESS, THE BACKFLOW AND
 GREASE INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED
 PRIOR TO APPROVAL OF THE PLUMBING REVISION. YOU CAN
 SUBMIT AN APPLICATION TBD (TO BE DETERMINED) IF YOU DO
 NOT HAVE A CONTRACTOR SELECTED BY EMAILING A COMPLETED
 PERMIT APPLICATION TO [email protected] . YOU
 WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS.
 YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT
 THE APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND
 THAT YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME.
 AFTER YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA
 EMAIL AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 NEW COMMENTS BASED ON RESUBMITTED PLANS AND EMAIL
 CORRESPONDENCE WITH THE ENGINEER.
  
 1) SHEETS A-1.2.1, P-2.2.1, P-5.2.4: MISSING FROM THE
 NEW PLUMBING FIXTURE CALCULATIONS AND APPARENTLY FROM
 THE PLAN IS THE REQUIRED SERVICE SINK. THE CALCULATIONS
 DO OMIT VITAL INFORMATION INCLUDING THE OCCUPANCY
 CLASSIFICATIONS AND OCCUPANT LOADS FOR EACH
 CLASSIFICATION, HOWEVER BASED ON THE PLANS AND TABLE
 403.1 IT APPEARS A COMPLIANT NUMBER OF WATER CLOSETS
 AND LAVATORIES HAVE BEEN PROVIDED FOR THE POOL, AND THE
 A AND B OCCUPANCIES. IT IS ACKNOWLEDGED THAT FUTURE
 BATHROOMS WILL UNDER THE RETAIL BUILD-OUT PERMIT.
  
 2) P-2.2.1 & P-5.2.4: 2ND REQUEST TO REVISE THESE
 SHEETS TO SHOW POOL WASTEWATER DISCHARGE DECHLORINATED
 AND DRAINED INTO THE STORM SYSTEM.
  
 3) P-5.2.4: RISER #14 SHOWN IN THE ISO IS NOT SHOWN ON
 RISER SHEETS P-5.2.2 OR P-5.2.3- SEC. 107.2.1 WPB.
  
 4) P-2.2.1 & P-5.2.4: THE 8-INCH MAIN BUILDING DRAIN
 LINE SHOWING 1622 DFU'S IS UNDERSIZED PER TABLE
 710.1(1) AT 1/8-INCH PER FT. SLOPE.
  
 5) P-5.2.6: THE EQUIPMENT SCHEDULES FOR THE STORAGE AND
 TANKLESS WATER HEATERS SHOWN ON THE ISO ARE NOT SHOWN
 ON SHEET P-6.2.2 AND NO INSTALLATION DETAILS PROVIDED
 SUCH AS THE DETAIL PROVIDED FOR THE APARTMENT UNITS ON
 P-6.2.1. THE DETAIL SHOULD SHOW THE MASTER THERMOSTATIC
 MIXING VALVE AND THE MEANS OF CONTROLLING EXPANSION-
 SECS. 607.1.1 & 607.3.
  
 6) P-5.2.6: NO INFO OR DETAILS PROVIDED FOR REQUIRED
 TEMPERED WATER DELIVERY AT LAVS, MASTER THERMOSTATIC
 MIXING VALVES AT WATER HEATERS TO LIMIT HOT WATER
 TEMPERATURE DELIVERY, AND NO HW PIPE INSULATION SPECS-
 SECS. 419.5, 607.1.1, 606.2.1, AND TABLE C403.2.10.
  
 7) P-5.2.6: THE LENGTHS OF HW FIXTURE SUPPLY PIPES TO
 THE LAVS IN GANG BATHROOM ARE EXCEEDING THE MAX 2FT.
 ALLOWABLE LENGTHS- TABLE C404.5.1.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  