2022-10-31 11:49:38PERMIT 22100341- REVISED PLUMBING PLANS DENIED.
 10/28/22
  
 COMMENTS.
  
 1) SHEET P-5.2.6: PLEASE REVISE THE RISER TO SHOW THE
 1-INCH COMMERCIAL SERVICE LINE RUN TO THE FUTURE RETAIL
 SPACE- SEC. 107.3.5.1.3 FBC P. SHOW A SHUT-OFF VALVE
 AND CAP WILL PROVIDED AT THE ENTRANCE TO THE RETAIL
 SPACE.
 2) P-5.2.6: PROVIDE CORRELATING TEXT FOR THE NUMBERED
 NOTES 1-4 ON THE RISER- SEC. 107.2.1 WPB.
  
  
 3) P-5.2.6: PROVIDE AN RPZ BACKFLOW PREVENTER FOR THE
 WATER LINE TO THE SPA EQUIPMENT- SEC. 608.17.4.1 FBC P
 AND SECS. C, D, & E- WPB CROSS CONNECTION MANUAL.
 PLEASE PROVIDE EQUIPMENT SCHEDULES FOR BOTH THE SPA AND
 POOL BF PREVENTERS- SEC. 608.3 FBC P.
  
 4) P-2.2.1: DETAIL P-6 FOR POOL AND SPA BACKWASH
 DRAINAGE IS REFERENCED ON THE PLAN. THE DETAIL IS
 11/P-6.2.1 WHICH WAS NOT PROVIDED BUT REVIEW OF THE
 MAIN PLUMBING PLANS SHOWS THE POOL BACKWASH DRAINING
 INTO THE SANITARY SYSTEM WHICH IS PROHIBITED PER SEC.
 90-126 (5) WPB. PLEASE NOTE THE FOLLOWING:
  
 SWIMMING POOL WATER SHALL NOT BE DISCHARGED TO SANITARY
 SEWER WITHOUT PRIOR APPROVAL FROM THE PUBLIC UTILITIES
 DEPARTMENT.
 SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY
 STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED
 ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM
 BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER???S
 SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW
 AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL
 WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED:
 THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH TO
 KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE
 INLET).
 NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE
 INLET TO DISCHARGE EFFLUENT.
 WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE ALLOWED
 TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS
 PROPERTY BEFORE DISCHARGING ON CITY PROPERTY.
 DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING
 PROPERTY.
 FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT O&M
 SUPERINTENDENT STEPHON HARRIS AT [email protected] OR
 561-822-2168.
 FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, PLEASE
 CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE
 SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561)
 822-2062 OR [email protected].
  
 5) P-2.2.2.1: PLEASE SHOW THE LOCATION OF THE FUTURE
 SANITARY DRAIN PIPING FOR THE RETAIL SPACE. THIS SPACE
 APPEARS TO BE ISOLATED FROM THE MAIN FLOOR. PLEASE
 CLARIFY IF PLUMBING FIXTURES FOR THE OCCUPANTS WILL BE
 PROVIDED IN ACCORDANCE WITH TABLE 403.1.
  
 6) SHEETS P-2.2.3, P-2.2.5 & P-5.2.5: PLEASE PROVIDE A
 DIMENSIONED BRIDGE ROOF DRAINAGE PLAN THAT SHOWS THE
 LOCATIONS OF THE PRIMARY AND SECONDARY (OVERFLOW) ROOF
 DRAINS, RAINFALL RATE, AND GPM FLOW AT THE RD LOCATION-
 SEC. 1105.1 & 1106.1 FBC P.
  
 7) PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR
 THE POTABLE WATER BACKFLOW PREVENTER, GREASE
 INTERCEPTOR, IRRIGATION, IRRIGATION BACKFLOW, AND POOL.
 IF REQUESTED GAS CAN ALSO BE UNDER A SEPARATE PERMIT.
 DUE TO A CHANGE IN PROCESS, THE BACKFLOW AND GREASE
 INTERCEPTOR PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR
 TO APPROVAL OF THE PLUMBING REVISION. YOU CAN SUBMIT AN
 APPLICATION TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A
 CONTRACTOR SELECTED BY EMAILING A COMPLETED PERMIT
 APPLICATION TO [email protected] . YOU WILL
 RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD PLANS. YOU
 MAY UPLOAD PLANS AND PAY FEES AT A FUTURE DATE, BUT THE
 APPLICATION IS REQUIRED AT THIS TIME. WE RECOMMEND THAT
 YOU PAY FEES AND UPLOAD PLANS AT THE SAME TIME. AFTER
 YOU HAVE THE PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL
 AND I WILL CHANGE THE REVIEW STATUS TO PASS.
  
 8) SHEET- P-2.2.2.1: THE POOL IS UNDER SEPARATE PERMIT
 HOWEVER PLEASE SHOW THE LOCATIONS OF THE REQUIRED
 SANITARY FACILITIES AND PROVIDE PLUMBING FIXTURE
 CALCULATIONS PER TABLES 403.1, 403.6, AND SEC. 403.1.1
 FBC P. THE PLAN APPEARS TO SHOW THE BATHROOMS ON THE
 FIRST FLOOR ARE FOR OCCUPANTS OF THE POOL AND DECK, AND
 THE OCCUPANTS OF THE BUILDING- PLEASE CLARIFY.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  