2023-01-04 16:23:27 | 2ND REVIEW FBC-2020 PLUMBING |
| PERMIT- 22100340 |
| 1/4/2023 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED |
| BELOW WITH ADDITIONAL NOTES FOR CLARIFICATION. |
| CIELO NORTH- PERMIT REVISION-22100340 PLUMBING REVIEW |
| COMMENTS |
| |
| 1) 2ND REQUEST. SHEETS A-1.1.1 & P-2.1.1: PLUMBING |
| FIXTURE CALCULATIONS NOT PROVIDED- TABLE 403.1 & SEC. |
| 403.1.1. PLEASE PROVIDE A SCHEDULE THAT SHOWS THE |
| REQUIRED AND PROVIDED NUMBER OF FIXTURES FOR THE A & B |
| OCCUPANCIES AND OCCUPANT LOADS SHOWN ON THE PLAN. IT |
| APPEARS THE SINGLE-OCCUPANT TOILET ROOM SHOWN ON THE |
| PLAN WITH ONE WATER CLOSET AND ONE LAVATORY MAY MEET |
| THE REQUIRMENT HOWEVER THE REQUIRED DRINKING FOUNTAINS |
| AND SERVICE SINK ARE NOT ACCOINTED FOR OR SHOWN ON THE |
| PLANS. |
| |
| 2) 2ND REQUEST. AT A MINIMUM, PERMIT APPLICATIONS FOR |
| THE POTABLE WATER BACKFLOW PREVENTER AND GREASE |
| INTERCEPTOR ARE S REQUIRED FOR THE PLUMBING PLAN REVIEW |
| TO BE APPROVED. |
| PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR THE |
| POTABLE WATER BACKFLOW PREVENTER, GREASE INTERCEPTOR, |
| IRRIGATION, IRRIGATION BACKFLOW, AND POOL. IF REQUESTED |
| GAS CAN ALSO BE UNDER A SEPARATE PERMIT. DUE TO A |
| CHANGE IN PROCESS, THE BACKFLOW AND GREASE INTERCEPTOR |
| PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR TO APPROVAL |
| OF THE PLUMBING REVISION. YOU CAN SUBMIT AN APPLICATION |
| TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR |
| SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO |
| [email protected] . YOU WILL RECEIVE INSTRUCTIONS |
| TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND |
| PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS |
| REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES |
| AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE |
| PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL |
| CHANGE THE REVIEW STATUS TO PASS. |
| P-2.1.1: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR |
| THE POTABLE WATER BACKFLOW PREVENTER, GREASE |
| INTERCEPTOR, IRRIGATION, AND THE IRRIGATION BACKFLOW. |
| PLEASE ADD THESE ITEMS TO THE DEFERRED SUBMITTALS LIST |
| FOR CLARIFICATION- SEC. 105.1 & 107.2.1 WPB. |
| DEPARTMENT, (561) 822-2062 OR [email protected]. |
| |
| 5) 2ND REQUEST. P-2.1.1 & P-6.2.1. THE DETAILS DO AND |
| NOTES DO NOT INDICATE THE ALARMS WILL BE PROVIDED: THE |
| ELEVATOR AND TRASH ROOM SUMP PUMPS SHALL BE EQUIPPED |
| WITH OIL ALARMS OR THE SUMP DISCHARGE SHALL BE CONVEYED |
| TO AN OIL SEPARATOR(S)- SEC. 1003.4 FBC P. |
| |
| 6) 2ND REQUEST. THE DETAIL ON P-6.1.1 SHOWS A 2-INCH |
| CONDENSATE PIPE DISCHARGING ONTO GRADE 8-INCHES AWAY |
| FROM THE BUILDING. THIS IS NOT AN APPROVED PLACE OF |
| DISPOSAL PER SEC. 314.2.1. PLEASE PROVIDE PIPE |
| CONNECTION TO STORM DRAIN OR DISCHARGE TO DRYWELL. |
| P-2.1.1 NOTE 9: SHOW THE CONDENSATE DRAINAGE WILL BE |
| CONVEYED AWAY FROM THE BUILDING TO AN APPROVED PLACE OF |
| DISPOSAL SUCH AS THE STORM DRAIN OR A DRYWELL- SEC. |
| 314.2.1 FBC P. |
| |
| |
| 14) 2ND REQUEST TO SHOW LOCATIONS OF STORM DRAIN |
| CLEANOUTS. P-2.1.1, P-2.1.1G, P-5.1.5, & P-5.1.6: |
| PROVIDE CLEANOUTS FOR THE HORIZONTAL STORM DRAINS WHERE |
| THEY EXIT THE BUILDING AND CONNECT WITH LATERALS- SEC. |
| 1101.8 FBC P. |
| |
| 18) 2ND REQUEST. THE WATER HEATER DETAILS ON P-6.1.2 |
| ARE THE APARTMENT WATER HEATERS WHICH ARE APPROVED. |
| PROVIDE THE GROUND FLOOR STORAGE AND TANKLESS WATER |
| HEATER DETAILS P-2.1.1, P-5.1.7 & P-6.1.2: PROVIDE |
| EQUIPMENT SCHEDULES AND INSTALLATION DETAILS FOR THE |
| GROUND FLOOR WATER HEATERS SHOWN ON THE ISO- SEC. |
| 107.2.1 WPB. THE DETAIL SHOULD SHOW THE MEANS OF |
| LIMITING THE HOT WATER TEMPERATURE, AND THE HOT WATER |
| PIPE INSULATION SPECIFICATION- SECS. 607.1.1, 607.3 FBC |
| P, AND TABLE C403.2.10 FBC ENERGY. A) PROVIDE A |
| BACKFLOW PREVENTER FOR THE SUPPLY LINE TO THE ICE |
| MAKER- SEC. 608.3 FBC P. |
| |
| 19) 2ND REQUEST. P-5.1.7 & P-6.1.2: SHOW THE MEANS OF |
| PROVIDING TEMPERED WATER DELIVERY FROM THE GROUND FLOOR |
| LAVATORY IN THE BATHROOM- SEC. 419.5 FBC P. PLEASE NOTE |
| THAT TEMPERATURE LIMITING DEVICES (MIXING VALVES) SHALL |
| BE ASSE 1070 LISTED- SEC. 607.1.2. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |