Plan Review Notes
Plan Review Notes For Permit 22100340
Permit Number 22100340
Review Stop P
Sequence Number 2
Notes
Date Text
2023-01-04 16:23:272ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22100340
 1/4/2023
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. FAILED COMMENTS ARE LISTED
 BELOW WITH ADDITIONAL NOTES FOR CLARIFICATION.
 CIELO NORTH- PERMIT REVISION-22100340 PLUMBING REVIEW
 COMMENTS
  
 1) 2ND REQUEST. SHEETS A-1.1.1 & P-2.1.1: PLUMBING
 FIXTURE CALCULATIONS NOT PROVIDED- TABLE 403.1 & SEC.
 403.1.1. PLEASE PROVIDE A SCHEDULE THAT SHOWS THE
 REQUIRED AND PROVIDED NUMBER OF FIXTURES FOR THE A & B
 OCCUPANCIES AND OCCUPANT LOADS SHOWN ON THE PLAN. IT
 APPEARS THE SINGLE-OCCUPANT TOILET ROOM SHOWN ON THE
 PLAN WITH ONE WATER CLOSET AND ONE LAVATORY MAY MEET
 THE REQUIRMENT HOWEVER THE REQUIRED DRINKING FOUNTAINS
 AND SERVICE SINK ARE NOT ACCOINTED FOR OR SHOWN ON THE
 PLANS.
  
 2) 2ND REQUEST. AT A MINIMUM, PERMIT APPLICATIONS FOR
 THE POTABLE WATER BACKFLOW PREVENTER AND GREASE
 INTERCEPTOR ARE S REQUIRED FOR THE PLUMBING PLAN REVIEW
 TO BE APPROVED.
 PLEASE NOTE THAT SEPARATE PERMITS ARE REQUIRED FOR THE
 POTABLE WATER BACKFLOW PREVENTER, GREASE INTERCEPTOR,
 IRRIGATION, IRRIGATION BACKFLOW, AND POOL. IF REQUESTED
 GAS CAN ALSO BE UNDER A SEPARATE PERMIT. DUE TO A
 CHANGE IN PROCESS, THE BACKFLOW AND GREASE INTERCEPTOR
 PERMITS ARE REQUIRED TO BE SUBMITTED PRIOR TO APPROVAL
 OF THE PLUMBING REVISION. YOU CAN SUBMIT AN APPLICATION
 TBD (TO BE DETERMINED) IF YOU DO NOT HAVE A CONTRACTOR
 SELECTED BY EMAILING A COMPLETED PERMIT APPLICATION TO
 [email protected] . YOU WILL RECEIVE INSTRUCTIONS
 TO PAY FEES AND UPLOAD PLANS. YOU MAY UPLOAD PLANS AND
 PAY FEES AT A FUTURE DATE, BUT THE APPLICATION IS
 REQUIRED AT THIS TIME. WE RECOMMEND THAT YOU PAY FEES
 AND UPLOAD PLANS AT THE SAME TIME. AFTER YOU HAVE THE
 PERMIT(S) GENERATED, NOTIFY ME VIA EMAIL AND I WILL
 CHANGE THE REVIEW STATUS TO PASS.
 P-2.1.1: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 THE POTABLE WATER BACKFLOW PREVENTER, GREASE
 INTERCEPTOR, IRRIGATION, AND THE IRRIGATION BACKFLOW.
 PLEASE ADD THESE ITEMS TO THE DEFERRED SUBMITTALS LIST
 FOR CLARIFICATION- SEC. 105.1 & 107.2.1 WPB.
 DEPARTMENT, (561) 822-2062 OR [email protected].
  
 5) 2ND REQUEST. P-2.1.1 & P-6.2.1. THE DETAILS DO AND
 NOTES DO NOT INDICATE THE ALARMS WILL BE PROVIDED: THE
 ELEVATOR AND TRASH ROOM SUMP PUMPS SHALL BE EQUIPPED
 WITH OIL ALARMS OR THE SUMP DISCHARGE SHALL BE CONVEYED
 TO AN OIL SEPARATOR(S)- SEC. 1003.4 FBC P.
  
 6) 2ND REQUEST. THE DETAIL ON P-6.1.1 SHOWS A 2-INCH
 CONDENSATE PIPE DISCHARGING ONTO GRADE 8-INCHES AWAY
 FROM THE BUILDING. THIS IS NOT AN APPROVED PLACE OF
 DISPOSAL PER SEC. 314.2.1. PLEASE PROVIDE PIPE
 CONNECTION TO STORM DRAIN OR DISCHARGE TO DRYWELL.
 P-2.1.1 NOTE 9: SHOW THE CONDENSATE DRAINAGE WILL BE
 CONVEYED AWAY FROM THE BUILDING TO AN APPROVED PLACE OF
 DISPOSAL SUCH AS THE STORM DRAIN OR A DRYWELL- SEC.
 314.2.1 FBC P.
  
  
 14) 2ND REQUEST TO SHOW LOCATIONS OF STORM DRAIN
 CLEANOUTS. P-2.1.1, P-2.1.1G, P-5.1.5, & P-5.1.6:
 PROVIDE CLEANOUTS FOR THE HORIZONTAL STORM DRAINS WHERE
 THEY EXIT THE BUILDING AND CONNECT WITH LATERALS- SEC.
 1101.8 FBC P.
  
 18) 2ND REQUEST. THE WATER HEATER DETAILS ON P-6.1.2
 ARE THE APARTMENT WATER HEATERS WHICH ARE APPROVED.
 PROVIDE THE GROUND FLOOR STORAGE AND TANKLESS WATER
 HEATER DETAILS P-2.1.1, P-5.1.7 & P-6.1.2: PROVIDE
 EQUIPMENT SCHEDULES AND INSTALLATION DETAILS FOR THE
 GROUND FLOOR WATER HEATERS SHOWN ON THE ISO- SEC.
 107.2.1 WPB. THE DETAIL SHOULD SHOW THE MEANS OF
 LIMITING THE HOT WATER TEMPERATURE, AND THE HOT WATER
 PIPE INSULATION SPECIFICATION- SECS. 607.1.1, 607.3 FBC
 P, AND TABLE C403.2.10 FBC ENERGY. A) PROVIDE A
 BACKFLOW PREVENTER FOR THE SUPPLY LINE TO THE ICE
 MAKER- SEC. 608.3 FBC P.
  
 19) 2ND REQUEST. P-5.1.7 & P-6.1.2: SHOW THE MEANS OF
 PROVIDING TEMPERED WATER DELIVERY FROM THE GROUND FLOOR
 LAVATORY IN THE BATHROOM- SEC. 419.5 FBC P. PLEASE NOTE
 THAT TEMPERATURE LIMITING DEVICES (MIXING VALVES) SHALL
 BE ASSE 1070 LISTED- SEC. 607.1.2.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  