2022-11-01 16:38:17 | 1ST REVIEW FBC-2020 PLUMBING |
| PERMIT- 22100340 |
| 11/1/22 |
| |
| CODES IN EFFECT: |
| FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 |
| FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| CIELO NORTH- PERMIT REVISION-22100340 PLUMBING REVIEW |
| COMMENTS |
| |
| 1) A-1.1.1 & P-2.1.1: PLUMBING FIXTURE CALCULATIONS NOT |
| PROVIDED- TABLE 403.1 & SEC. 403.1.1. PLEASE PROVIDE A |
| SCHEDULE THAT SHOWS THE REQUIRED AND PROVIDED NUMBER OF |
| FIXTURES FOR THE OCCUPANCIES. IT IS ACKNOWLEDGED THAT |
| THE OCCUPANT LOADS OF THE RESIDENTIAL (APARTMENTS) AND |
| THE S-2 PARKING GARAGE CAN BE EXCLUDED FROM THE MIXED |
| OCCUPANCY CALCULATION HOWEVER THAT RESULTS WITH AN |
| OCCUPANT LOAD OF 124 TO PROVIDE PLUMBING FIXTURES FOR. |
| THE NUMBER CAN BE REDUCED FURTHER DOWN TO 68 IF THE |
| OCCUPANTS OF THE M FUTURE RETAIL ARE REMOVED HOWEVER |
| THAT WILL HAVE TO BE CLARIFIED ON THE PLAN BECAUSE NO |
| FUTURE SANITARY LINE IS SHOWN ON THE PLUMBING PLANS. |
| PLEASE NOTE THERE IS ONLY ONE SINGLE-OCCUPANT TOILET |
| ROOM SHOWN ON THE PLAN WITH ONE WATER CLOSET AND ONE |
| LAVATORY WHICH IS DEFICIENT FOR THE MINIMUM 68 |
| OCCUPANTS OR THE MAXIMUM 124 OCCUPANTS. ALSO MISSING |
| ARE THE REQUIRED DRINKING FOUNTAINS AND SERVICE SINK- |
| TABLE 403.1. |
| |
| 2) P-2.1.1: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR |
| THE POTABLE WATER BACKFLOW PREVENTER, GREASE |
| INTERCEPTOR, IRRIGATION, AND THE IRRIGATION BACKFLOW. |
| PLEASE ADD THESE ITEMS TO THE DEFERRED SUBMITTALS LIST |
| FOR CLARIFICATION- SEC. 105.1 & 107.2.1 WPB. PLEASE |
| NOTE THAT A GAS METER IS SHOWN ON P-1.1.0 HOWEVER NO |
| GAS PLANS HAVE BEEN PROVIDED. WILL GAS ALSO BE UNDER |
| SEPARATE PERMIT? |
| |
| 3) P-2.1.1, P-5.1.6: THE WASTEWATER FROM THE FOUNTAIN |
| IS DRAINING INTO THE SUMP PIT AND THEN DISCHARGING INTO |
| THE STORM SYSTEM. PLEASE NOTE CHLORINATED POOL OR |
| FOUNTAIN WASTE WATER SHALL NOT DRAIN INTO THE STORM |
| SYSTEM UNLESS IT HAS BEEN DECHLORINATED PER SEC. 90-205 |
| (1) WPB CODE OF ORDINANCES. PLEASE REVIEW THE FOLLOWING |
| INFORMATION CONCERNING THE FOUNTAIN WASTEWATER. |
| |
| SWIMMING POOL WATER MAY BE DISCHARGED TO THE CITY |
| STORMWATER SEWER ONLY IF THE WATER IS DECHLORINATED |
| ACCORDING TO SECTION 90-205(1) OF THE CITY OF WEST PALM |
| BEACH CODE OF ORDINANCES. SUBMIT THE MANUFACTURER???S |
| SPECIFICATION FOR THE DICHLORINATION SYSTEM FOR REVIEW |
| AND STAMPING BEFORE THE INSPECTION. AT THE TIME OF POOL |
| WATER DISCHARGE, THE FOLLOWING WILL BE REQUIRED: |
| ??? THE RECEIVING INLET MUST BE PROTECTED (FILTER CLOTH |
| TO KEEP EXCESS SEDIMENTS FROM ROADWAY WASHING INTO THE |
| INLET). |
| ??? NO DISCHARGE HOSE CAN BE DIRECTLY INSERTED INTO THE |
| INLET TO DISCHARGE EFFLUENT. |
| ??? WHENEVER POSSIBLE, DISCHARGE EFFLUENT SHALL BE |
| ALLOWED TO FILTER THROUGH GRASS AREA ON THE POOL OWNERS |
| PROPERTY BEFORE DISCHARGING ON CITY PROPERTY. |
| ??? DISCHARGE SHALL NOT FLOOD STREETS OR NEIGHBORING |
| PROPERTY. |
| ??? FOR TECHNICAL QUESTIONS, DON'T HESITATE TO CONTACT |
| O&M SUPERINTENDENT STEPHON HARRIS AT [email protected] OR |
| 561-822-2168. |
| ??? FOR STORMWATER DISCHARGE COMPLIANCE QUESTIONS, |
| PLEASE CONTACT CHRIS JACKSON, ENVIRONMENTAL COMPLIANCE |
| SPECIALIST III, PUBLIC UTILITIES DEPARTMENT, (561) |
| 822-2062 OR [email protected]. |
| |
| 4) P-2.1.1 & P-6.2.2: PLEASE PROVIDE AN EQUIPMENT |
| SCHEDULE FOR THE COURTYARD SUMP PUMP LISTING MAKE AND |
| MODEL AND ELECTRICAL DATA- SEC. 712.3 FBC P. |
| |
| 5) P-2.1.1 & P-6.2.1: THE ELEVATOR AND TRASH ROOM SUMP |
| PUMPS SHALL BE EQUIPPED WITH OIL ALARMS OR THE SUMP |
| DISCHARGE SHALL BE CONVEYED TO AN OIL SEPARATOR(S)- |
| SEC. 1003.4 FBC P. |
| |
| 6) P-2.1.1 NOTE 9: SHOW THE CONDENSATE DRAINAGE WILL BE |
| CONVEYED AWAY FROM THE BUILDING TO AN APPROVED PLACE OF |
| DISPOSAL SUCH AS THE STORM DRAIN OR A DRYWELL- SEC. |
| 314.2.1 FBC P. |
| |
| 7) P-2.1.1: PROVIDE A NOTE TO SHOW THE LOCATIONS OF THE |
| WATER HEATER DRAIN PAN LINE TERMINATION LOCATIONS- SEC. |
| 504.7.2 FBC P. |
| |
| 8) P-6.1.2: PROVIDE A BACKFLOW PREVENTER FOR THE WATER |
| LINE SUPPLY LINE TO THE TRASH CHUTE- SEC. 608.3 FBC P. |
| PLEASE INCLUDE AN EQUIPMENT SCHEDULE FOR THE DEVICE ON |
| SHEET P-6.2.2. |
| |
| 9) P-5.1.1, P-6.2.2: PROVIDE A BACKFLOW PREVENTER FOR |
| THE WATER LINE SUPPLY LINE TO THE TRASH CHUTE- SEC. |
| 608.3 FBC P. PLEASE INCLUDE AN EQUIPMENT SCHEDULE FOR |
| THE DEVICE ON SHEET P-6.2.2. |
| |
| 10) P-5.1.1: SUBMIT MANUFACTURER'S SPECIFICATIONS FOR |
| THE SPEARS PERFORATED CAPS. THE CAPS WILL BE INSTALLED |
| IN PLENUM ENCLOSURES AND SHALL BE NONCOMBUSTIBLE OR |
| SHALL BE LISTED AND LABELED AS HAVING A FLAME SPREAD |
| INDEX OF NOT MORE THAN 25 AND A SMOKE-DEVELOPED INDEX |
| OF NOT MORE THAN 50 WHEN TESTED IN ACCORDANCE WITH ASTM |
| E84 OR UL 723- SEC. 602.2.1 FBC M. IT APPEARS THE CAPS |
| WILL BE VENTING THE TRAPS WHICH IS PROHIBITED IN PLENUM |
| ENCLOSURES- SECS. 903.5, 905.1 & 918.8. |
| |
| 11) P-5.1.4: IT APPEARS THAT THERE ARE MISSING VENT |
| STACKS THAT ARE REQUIRED TO BE CONNECTED AT THE BASE OF |
| THE SOIL STACKS (#2, 5, 6, 9, & 11). THE VENT STACK |
| POINTS OF CONNECTION SHALL BE DOWNSTREAM OF THE SOIL |
| STACK BASES WITHIN A DISTANCE OF 10 TIMES THE DIAMETER |
| OF THE SOIL STACK. PLEASE NOTE P-5.1.4 SHOWS STACK #12 |
| WHICH IS NOT SHOWN ON THE RISER DRAWINGS- P-5.1.2 & |
| P-5.1.3. |
| |
| 12) P-5.1.4: THE DRAWING SHOWS MANY STACKS COMBINED |
| TOGETHER BEFORE CONNECTING TO THE BUILDING DRAIN SUCH |
| AS (1&2), (4&5), (1&10), (11,3,4). WASTE AND SOIL |
| STACKS CANNOT BE COMBINED TOGETHER BECAUSE EACH |
| REQUIRES A SEPARATE VENT, AND EACH STACK SHALL CONNECT |
| SEPARATELY TO THE BUILDING DRAIN- SEC. 913.2 FBC P. |
| |
| 13) P-2.1.1 & P-5.1.4: THE REVISED PLANS SHOW A |
| BAR/CAFE WITH THE DRAINAGE FROM THE SINK AND DISHWASHER |
| DISCHARGING TO THE SANITARY WHICH MAY BE PROHIBITED IF |
| THE DRAINAGE IS GREASE LADEN- SEC. 1003.3.1 FBC P. MORE |
| INFORMATION WILL BE REQUIRED CONCERNING THE FOOD AND |
| DRINK OPERATIONS IN THE BAR/CAFE. A) DRAINAGE FROM THE |
| ICEMAKER IN THE BAR DISCHARGE TO THE SANITARY. |
| |
| 14) P-2.1.1, P-2.1.1G, P-5.1.5, & P-5.1.6: PROVIDE |
| CLEANOUTS FOR THE HORIZONTAL STORM DRAINS WHERE THEY |
| EXIT THE BUILDING AND CONNECT WITH LATERALS- SEC. |
| 1101.8 FBC P. |
| |
| 15) P-2.1.6, P-5.1.5 & P-5.1.6: ROOF DRAINAGE VERTICAL |
| AND HORIZONTAL DRAIN PIPE SIZES ARE DETERMINED BY GPM |
| FLOW. PLEASE CONVERT THE SQUARE FOOTAGE TOTALS ON THE |
| DRAWINGS TO GPM TO VERIFY VERTICAL LEADERS AND |
| HORIZONTAL DRAINS ARE SIZED IN COMPLIANCE WITH TABLES |
| 1106.2 & 1006.3 FBC P. |
| |
| A) P-2.1.6, P-2.1.4G: PLEASE PROVIDE ADDITIONAL ROOF |
| DRAINAGE INFORMATION FOR THE MAIN BUILDING AND LEVEL 5 |
| TERRACE OF THE GARAGE INCLUDING RAINFALL RATE, SQUARE |
| FOOTAGE BREAKDOWN THAT INCLUDES THE PARAPET WALLS, AND |
| AN EMERGENCY SCUPPER DETAIL- SECS. 1106.1, 1106.4, AND |
| 1106.5 FBC P. |
| |
| B) P-2.1.4G: PLEASE DETAIL EMERGENCY (OVERFLOW) |
| DRAINAGE FOR THE TERRACE AND DISPOSAL LOCATION- SEC. |
| 1106.5 FBC P. |
| |
| 16) P-5.1.1, P-5.1.7: SHOW THE LOCATIONS OF FULL-OPEN |
| VALVES AT THE BASES OF THE WATER RISERS. THE NOTE ON |
| P-5.1.1 REFERENCING THE WATER HEATER DETAIL FOR |
| LOCATION DOES NOT APPEAR RELEVANT TO THE CODE |
| REQUIREMENT- SEC. 606.1(4) FBC P. |
| |
| 17) P-2.1.1: TO HELP EXPEDITE THE REVIEW PLEASE NOTE & |
| LABEL THE WATER SERVICE ENTRANCE INTO THE BUILDING AND |
| LABEL THE LOCATION OF THE DOMESTIC BOOSTER PUMP- SEC. |
| 107.2.1 WPB. |
| |
| 18) P-2.1.1, P-5.1.7 & P-6.1.2: PROVIDE EQUIPMENT |
| SCHEDULES AND INSTALLATION DETAILS FOR THE GROUND FLOOR |
| WATER HEATERS SHOWN ON THE ISO- SEC. 107.2.1 WPB. |
| IDENTIFY THE FIXTURE BEING SUPPLIED HOT WATER FROM THE |
| TANKLESS WATER HEATER SHOWN IN THE AREA OF THE TRASH |
| ROOM AND BOOSTER. THE DETAIL SHOULD SHOW THE MEANS OF |
| LIMITING THE HOT WATER TEMPERATURE, AND THE HOT WATER |
| PIPE INSULATION SPECIFICATION- SECS. 607.1.1, 607.3 FBC |
| P, AND TABLE C403.2.10 FBC ENERGY. A) PROVIDE A |
| BACKFLOW PREVENTER FOR THE SUPPLY LINE TO THE ICE |
| MAKER- SEC. 608.3 FBC P. |
| |
| 19) P-5.1.7 & P-6.1.2: SHOW THE MEANS OF PROVIDING |
| TEMPERED WATER DELIVERY FROM THE GROUND FLOOR LAVATORY |
| IN THE BATHROOM- SEC. 419.5 FBC P. PLEASE NOTE THAT |
| TEMPERATURE LIMITING DEVICES (MIXING VALVES) SHALL BE |
| ASSE 1070 LISTED- SEC. 607.1.2. |
| |
| 20) P-6.1.2: PLEASE SEE NOTE #8 AT THE WATER HEATER |
| DETAILS AND PROVIDE THE HW PIPE INSULATION |
| SPECIFICATIONS- TABLE C403.2.10 FBC ENERGY. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. |
| |