Plan Review Notes
Plan Review Notes For Permit 22100223
Permit Number 22100223
Review Stop P
Sequence Number 1
Notes
Date Text
2022-11-01 08:07:501ST PLUMBING REVIEW
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - IN REVIEW OF THE CODE CASE
 PICTURES, YOU HAVE NOT DETAILED THE WATER HEATER
 (BOTTOM FED) AND YOU ARE ONLY SHOWING ONE OF THE TWO
 WASHING MACHINES,
  
 2. 2020 FPC 607.1.1 - PLEASE SHOW COMPLIANCE WITH THE
 LIMITING FOR HOT WATER DELIVERY. THE THERMOSTAT ON THE
 WATER CANNOT SERVE AS THE LIMITING MEANS FOR HOT OR
 TEMPERED WATER. A MIXING DEVICE IS REQUIRED FOR THIS
 SECTION. THE DEVICE MUST COMPLY WITH ASSE 1017 AND MUST
 BE INSTALLED AT THE HOT WATER SOURCE PER 2020 FPC
 613.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  