Plan Review Notes For Permit 22100222 |
Permit Number |
22100222 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-10-18 09:00:36 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC B 107.2.1. SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL14207-R26 HAS BEEN REVISED TO FL14207-R28. | | PLEASE PROVIDE THE FOLLOWING: COVER PAGE, EVALUATION | | REPORT PAGES 1-4 AND INSTALLATION INSTRUCTIONS FOR | | SYSTEM USED. ALL APPLICABLE DETAILS AND ATTACHMENTS | | MUST BE CLEARLY IDENTIFIED ON THE PRODUCT APPROVAL | | DRAWINGS. | | 2. FBC B 107.2.1 FBC EB 706.1 SUBMITTED ROOF | | DRAWING/SKETCH LISTS FLAT/LOW ROOF SLOPE AS 0:12; LOW | | SLOPE ROOFS MUST SHOW POSITIVE DRAINAGE. PROVIDE METHOD | | OF PROVIDING POSITIVE DRAINAGE. | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|