Plan Review Notes For Permit 22100217 |
Permit Number |
22100217 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-12-07 13:06:29 | BUILD OUT | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) PLEASE SHOW THE CEILING HEIGHT - FBC 1208.2 | | | | 2) ACCESSIBLE RESTROOM = PLEASE USE THE WORDS | | "REFLECTIVE SURFACE" WHEN REFERRING TO THE DIMENSION | | FROM THE FLOOR TO THE BOTTOM OF THE MIRROR - FBC 603.3 | | MIRRORS. | | MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS SHALL | | BE INSTALLED WITH THE BOTTOM EDGE OF THE REFLECTING | | SURFACE 40 INCHES (1015 MM) MAXIMUM ABOVE THE FINISH | | FLOOR OR GROUND. | | | | 3) ACCESSIBLE RESTROOM = THE CLEAR FLOOR SPACE FOR THE | | INSWING DOOR IS SHOWN ON TOP OF THE TOILET - SHOULD BE | | CLEAR FLOOR SPACE - FBC 603.2.3 (2) WHERE THE TOILET | | ROOM OR BATHING ROOM IS FOR INDIVIDUAL USE AND A CLEAR | | FLOOR SPACE COMPLYING WITH 305.3 IS PROVIDED WITHIN THE | | ROOM BEYOND THE ARC OF THE DOOR SWING, DOORS SHALL BE | | PERMITTED TO SWING INTO THE CLEAR FLOOR SPACE OR | | CLEARANCE REQUIRED FOR ANY FIXTURE. | | | | 4) ACCESSIBLE RESTROOM = PLEASE SHOW THE DOOR | | MANEUVERING CLEARANCE INSIDE THE RESTROOM TO EXIT THE | | RESTROOM - FBC 404.2.4 |
|