2023-03-20 15:50:22 | NEW SFR |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) DOOR NUMBER 7 ENTRY TO THE BEDROOM WILL ALSO NEED TO |
| MEET THE 29" CLEAR OPENING TO HAVE ACCESS TO THE |
| BATHROOM INSIDE - FBC R320.1.1 ALL NEW SINGLE-FAMILY |
| HOUSES, DUPLEXES, TRIPLEXES, CONDOMINIUMS AND |
| TOWNHOUSES SHALL PROVIDE AT LEAST ONE BATHROOM, LOCATED |
| WITH MAXIMUM POSSIBLE PRIVACY, WHERE BATHROOMS ARE |
| PROVIDED ON HABITABLE GRADE LEVELS, WITH A DOOR THAT |
| HAS A 29-INCH (737 MM) CLEAR OPENING. FBC 404.2.3 CLEAR |
| OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE |
| MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP, |
| WITH THE DOOR OPEN 90 DEGREES. |
| |
| 2) DRAWINGS SHOW TO USE NAILS FOR THE TILE ROOF |
| ATTACHMENT - YOU WILL NEED TO SPECIFY THE TYPE OF NAIL |
| AND THE AMOUNT OF NAILS TO MEET THE REQUIRED UPLIFT - |
| THE PRODUCT APPROVAL HAS OPTIONS - PRODUCT APPROVAL |
| PROVIDED FOR THE ROOF TILE - PLEASE CIRCLE THE ROOF |
| TILE ATTACHMENT TYPE IN THE PRODUCT APPROVAL - IF USING |
| ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL. |
| |
| 3) MULTIPLE ROOF NOTES ON THE DRAWINGS SHOW SHINGLES |
| FOR THE ROOF SYSTEM. |
| |
| 4) THE 2ND FLOOR BEDROOM #2 - THE WINDOWS DO NOT SEEM |
| TO MEET THE EMERGENCY ESCAPE REQUIREMENT OF 5.7 SQUARE |
| FEET - FBC R310.2.1 MINIMUM OPENING AREA. |
| EMERGENCY AND ESCAPE RESCUE OPENINGS SHALL HAVE A NET |
| CLEAR OPENING OF NOT LESS THAN 5.7 SQUARE FEET (0.530 |
| M2). THE NET CLEAR OPENING DIMENSIONS REQUIRED BY THIS |
| SECTION SHALL BE OBTAINED BY THE NORMAL OPERATION OF |
| THE EMERGENCY ESCAPE AND RESCUE OPENING FROM THE |
| INSIDE. |
| |
| |
| |
| |
| |
| |
| |