Plan Review Notes
Plan Review Notes For Permit 22100154
Permit Number 22100154
Review Stop B
Sequence Number 2
Notes
Date Text
2023-03-20 15:50:22NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DOOR NUMBER 7 ENTRY TO THE BEDROOM WILL ALSO NEED TO
 MEET THE 29" CLEAR OPENING TO HAVE ACCESS TO THE
 BATHROOM INSIDE - FBC R320.1.1 ALL NEW SINGLE-FAMILY
 HOUSES, DUPLEXES, TRIPLEXES, CONDOMINIUMS AND
 TOWNHOUSES SHALL PROVIDE AT LEAST ONE BATHROOM, LOCATED
 WITH MAXIMUM POSSIBLE PRIVACY, WHERE BATHROOMS ARE
 PROVIDED ON HABITABLE GRADE LEVELS, WITH A DOOR THAT
 HAS A 29-INCH (737 MM) CLEAR OPENING. FBC 404.2.3 CLEAR
 OPENINGS OF DOORWAYS WITH SWINGING DOORS SHALL BE
 MEASURED BETWEEN THE FACE OF THE DOOR AND THE STOP,
 WITH THE DOOR OPEN 90 DEGREES.
  
 2) DRAWINGS SHOW TO USE NAILS FOR THE TILE ROOF
 ATTACHMENT - YOU WILL NEED TO SPECIFY THE TYPE OF NAIL
 AND THE AMOUNT OF NAILS TO MEET THE REQUIRED UPLIFT -
 THE PRODUCT APPROVAL HAS OPTIONS - PRODUCT APPROVAL
 PROVIDED FOR THE ROOF TILE - PLEASE CIRCLE THE ROOF
 TILE ATTACHMENT TYPE IN THE PRODUCT APPROVAL - IF USING
 ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL.
  
 3) MULTIPLE ROOF NOTES ON THE DRAWINGS SHOW SHINGLES
 FOR THE ROOF SYSTEM.
  
 4) THE 2ND FLOOR BEDROOM #2 - THE WINDOWS DO NOT SEEM
 TO MEET THE EMERGENCY ESCAPE REQUIREMENT OF 5.7 SQUARE
 FEET - FBC R310.2.1 MINIMUM OPENING AREA.
 EMERGENCY AND ESCAPE RESCUE OPENINGS SHALL HAVE A NET
 CLEAR OPENING OF NOT LESS THAN 5.7 SQUARE FEET (0.530
 M2). THE NET CLEAR OPENING DIMENSIONS REQUIRED BY THIS
 SECTION SHALL BE OBTAINED BY THE NORMAL OPERATION OF
 THE EMERGENCY ESCAPE AND RESCUE OPENING FROM THE
 INSIDE.
  
  
  
  
  
  
  