2023-02-15 09:15:291ST REVIEW FBC-2020 RES. GAS
 PERMIT- 22100154
 2/16/23
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P1: IN ORDER TO HELP EXPEDITE THE REVIEW OF
 THE GAS PIPING SYSTEM, PLEASE IDENTIFY THE TYPE OF PIPE
 AT EACH SECTION OR BRANCH SHOWN IN THE RISER, AND
 PROVIDE A SEPARATE FLOOR PLAN DRAWING THAT THAT SHOWS
 THE EXTERIOR AND INTERIOR GAS PIPING RUNS AND APPLIANCE
 LOCATIONS- SEC. 107.2.1 WPB AND SEC. G2413.1 FBC RES.
 A) FLOOR PLAN DRAWING: PLEASE SHOW THE LOCATIONS AND
 TERMINATION POINTS OF ALL SLEEVES AND CONDUITS INTERIOR
 AND EXTERIOR OF THE BUILDING AND HOW THE OPEN ENDS WILL
 BE SEALED AND VENTED WHERE REQUIRED- SEE SECS.
 G2415.14.1- G2415.14.2 FBC RES.
  
 2) P1: PE PIPING IS RATED AND LABELED FOR DIRECT
 UNDERGROUND BURIAL AND DOES NOT REQUIRE A PVC CONDUIT
 OR SLEEVE. PLEASE CORRECT THE NOTE ON THE DRAWING, AND
 NOTE THAT PE PIPING SHALL NOT BE INSTALLED UNDER THE
 BUILDING WHETHER SLEEVED OR NOT AND REQUIRES
 INSTALLATION OF A TRACER WIRE- SEE SECS. G2417.1-
 G2417.3 FBC RES.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  