2023-02-27 13:48:12 | NEW SFR |
| REVIEWED BY ROGER MCPHERSON |
| 561-805-6716 |
| [email protected] |
| CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 |
| AMENDMENT |
| |
| CORRECTIONS NEEDED - |
| |
| 1) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE - FBC |
| R807.1 |
| |
| 2) FBC R320.1.1 ALL NEW SINGLE-FAMILY HOUSES, DUPLEXES, |
| TRIPLEXES, CONDOMINIUMS AND TOWNHOUSES SHALL PROVIDE AT |
| LEAST ONE BATHROOM, LOCATED WITH MAXIMUM POSSIBLE |
| PRIVACY, WHERE BATHROOMS ARE PROVIDED ON HABITABLE |
| GRADE LEVELS, WITH A DOOR THAT HAS A 29-INCH (737 MM) |
| CLEAR OPENING. FBC 404.2.3 CLEAR OPENINGS OF DOORWAYS |
| WITH SWINGING DOORS SHALL BE MEASURED BETWEEN THE FACE |
| OF THE DOOR AND THE STOP, WITH THE DOOR OPEN 90 |
| DEGREES. |
| |
| 3) PLEASE SHOW THE STAIR HAND RAIL DETAILS - FBC |
| R311.7.8 |
| |
| 4) PLEASE SHOW THE GUARD RAIL DETAILS - FBC R312.1 |
| |
| 5) PRODUCT APPROVAL PROVIDED FOR THE ROOF TILE - PLEASE |
| CIRCLE THE ROOF TILE ATTACHMENT TYPE IN THE PRODUCT |
| APPROVAL - IF USING ADHESIVE PLEASE PROVIDE THE |
| ADHESIVE PRODUCT APPROVAL. |
| |
| 6) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED |
| APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB |
| 107.3.4 |
| |
| 7) THE WINDOW SCHEDULE ON DRAWING A-5.0 SHOWS - DOUBLE |
| HUNG WINDOWS, CASEMENT WINDOWS, PUSH OUT FRENCH |
| CASEMENT WINDOWS - PLEASE PROVIDE PRODUCT APPROVALS FOR |
| ALL WINDOW TYPES SHOWN ON THE WINDOW SCHEDULE. |
| |
| 8) DRAWING C-1 DOES NOT SHOW AS DIGITALLY SIGNED IN |
| ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX |
| NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED |
| IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL |
| SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A |
| SPECIFIC TYPE OF E-SIGNATURE). |
| |