Plan Review Notes
Plan Review Notes For Permit 22100134
Permit Number 22100134
Review Stop B
Sequence Number 2
Notes
Date Text
2022-10-25 09:57:20JONATHAN BROOKS JR.
 BUILDING PLANS EXAMINER
 WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM
 PHONE (561) 805-6656
 EMAIL: [email protected]
  
 1ST REVIEW: FBC 2020 7TH EDITION
 FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020)
 FBC B = FBC BUILDING
 FBC R = FBC RESIDENTIAL
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC
 RESULTS: DENIED
 ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT
 TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT
 CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX.
  
 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT
 APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5;
 EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15);
 ULTIMATE WIND SPEED (200). ZONE 2 & ZONE 3 IS MARKED
 ???N/A??? WHICH INDICATES SYSTEM IS ???NOT
 APPLICABLE??? TO ZONE1 PRIME DESIGN PRESSURE
 REQUIREMENTS AND CANNOT BE USED. PRODUCT APPROVAL
 FL16709-R10 WILL NOT SATISFY EXPOSURE CATEGORY D
 ENCLOSED AREAS WITHOUT USING INSULATION. (OPTION SYSTEM
 W-3 EXPOSURE D, ENCLOSED, ULTIMATE WIND SPEED 170 MPH).
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  