Plan Review Notes For Permit 22100134 |
Permit Number |
22100134 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-10-25 09:57:20 | JONATHAN BROOKS JR. | | BUILDING PLANS EXAMINER | | WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM | | PHONE (561) 805-6656 | | EMAIL: [email protected] | | | | 1ST REVIEW: FBC 2020 7TH EDITION | | FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) | | FBC B = FBC BUILDING | | FBC R = FBC RESIDENTIAL | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC | | RESULTS: DENIED | | ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT | | TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT | | CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. | | | | 1. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT | | APPROVAL FL16709-R10 SELECTED OPTION FOR SYSTEM NO W-5; | | EXPOSURE (D); ENCLOSURE (ENCLOSED); ROOF HEIGHT (H<15); | | ULTIMATE WIND SPEED (200). ZONE 2 & ZONE 3 IS MARKED | | ???N/A??? WHICH INDICATES SYSTEM IS ???NOT | | APPLICABLE??? TO ZONE1 PRIME DESIGN PRESSURE | | REQUIREMENTS AND CANNOT BE USED. PRODUCT APPROVAL | | FL16709-R10 WILL NOT SATISFY EXPOSURE CATEGORY D | | ENCLOSED AREAS WITHOUT USING INSULATION. (OPTION SYSTEM | | W-3 EXPOSURE D, ENCLOSED, ULTIMATE WIND SPEED 170 MPH). | | | | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. | | |
|