2022-10-20 12:28:26 | FIRE REVIEW COMMENTS: | | | | (1) FOR CLARIFICATION, INDICATE THE DISTANCE IN FEET | | FROM THE NEAREST FIRE HYDRANT TO THE FDC. | | | | NFPA 14, 6.4.5.4 | | | | (2) PROVIDE DETAILS ON THE OMISSION OF FIRE SPRINKLER | | HEADS AT THE TOP OF THE ELEVATOR SHAFT AND THE ELEVATOR | | MACHINE ROOM. | | | | NFPA 13, 8.15.5 | | | | (3) PROVIDE DETAIL ON THE OMISSION OF FIRE SPRINKLER | | COVERAGE FOR THE ROOF TOP AMENITIES SPACE (PLACE OF | | ASSEMBLY THAT WILL INCLUDE COMBUSTIBLE | | MATERIALS/FURNITURE) ON LEVEL 8, AND THE PORTE COCHERE | | AND DROP OFF CANOPY ON THE FIRST (GROUND) LEVEL. | | | | NFPA 13, 8.15.7 | | | | C. WALKER | | | | 561-804-4762 | | | | [email protected] | | |
|