Plan Review Notes For Permit 22100111 |
Permit Number |
22100111 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-11-07 12:09:52 | 1. PLEASE SPECIFY WINDOW REPLACEMENT SIZE AT OPENINGS | | SHOWN AS EGRESS. FBC 107.2 | | 2. PLANS ARE NOT LEGIBLE. PLEASE SUBMIT LEGIBLE PLANS | | OR DETAILS. FBC 107.2 | | 3. INFILL DETAIL IS NOT LEGIBLE. PLEASE RESUBMIT | | LEGIBLE DETAILS. FBC 107.2 | | 4. PLEASE SUBMIT FLOOR PLAN SHOWING ALL OPENINGS MARKED | | EXISTING TO REMAIN OR MARKED WITH REPLACEMENT. FBC | | 107.2 | | 5. PLEASE SUBMIT WINDOW SCHEDULE. FBC 107.2 | | 6. PLEASE PROVIDE A FLASHING DETAIL, OR ADD A NOTE TO | | THE PLAN, DEMONSTRATING COMPLIANCE WITH FBC R 703.4 OR | | FBC B 1405.4. THIS IS ON PLANS BUT NOT LEGIBLE. FBC | | 107.2 | | DIGITAL SIGNATURE-DISAPPROVED | | 1. NEW INFILL AND DETAILED PLANS MUST BE SEALED BY | | EOR/AOR. | | |
|