Plan Review Notes
Plan Review Notes For Permit 22100018
Permit Number 22100018
Review Stop G
Sequence Number 1
Notes
Date Text
2022-10-05 16:21:271ST GAS REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
  
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2017 WPB AMENDS 107.2.1 - IT IS UNCLEAR ON THE RUN
 TO THE TANKLESS W/H, POOL HEATER AND BBQ - IS THIS LINE
 ABOVE GROUND OR BELOW? GALVANIZED PIPING CANNOT BE
 BELOW GRADE (2020 FRC G2415.11.1)
  
 2. 2017 WPB AMENDS 107.2.1 - ON YOUR ISOMETRIC, YOU
 SHOULD SHOW WHERE THE REGULATORS ARE, AND THE
 CORRESPONDING PRESSURES FOR THOSE REGULATORS.
  
 3. 2020 FRC G2439.5 - PROVIDE THE CALCULATION FOR THE
 NEED OR LACK OF NEED FOR MAKE UP AIR FOR THE DRYER.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  
 RYAN W. BROWN
 CHIEF PLUMBING INSPECTOR
 OFFICE: 561-805-6692
 CELL: 561-517-4293
 EMAIL: [email protected]
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved