2022-10-18 15:54:28 | 1ST REVIEW FMC |
| PERMIT: 22091344 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PROVIDE THE ENERGY CALCULATIONS FOR THE HOUSE. FEC |
| R101.5.1.1.1 |
| |
| 2) PROVIDE THE ENERGY CALCULATIONS FOR THE GARAGE. FEC |
| R101.5.1.1.1 |
| |
| 3) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| FOR THE HOUSE. FEC R403.7.1 |
| |
| 4) PROVIDE THE MECHANICAL EQUIPMENT SIZING CALCULATIONS |
| FOR THE GARAGE. FEC R403.7.1 |
| |
| 5) SHEET M-1.1: REMOVE THE RETURN AIR DUCT FROM THE |
| MASTER WALK-IN CLOSET. FRC M1602.2-4 |
| |
| 6) SHEET M-1.1 NOTE 4 STATES THAT THE REFRIGERATION |
| LINES ARE EXISTING WITHIN SPACE AT TIME OF |
| CONSTRUCTION. THERE WILL BE NO MODIFICATIONS ON THESE |
| LINES. THE APPLICATION STATES THIS IS A NEW |
| CONSTRUCTION. REMOVE THIS NOTE OR CORRECT THE |
| APPLICATION. FBC 107.3.5 |
| |
| 7) SHEET M-1.1: REVISE THE DRAWING TO SHOW THE REQUIRED |
| EXHAUST FAN AT THE TUB AREA OF THE MASTER BATH. FRC |
| R303.3 EXCEPTION. |
| |
| 8) SHEET M-1.2: NOTE 4 STATES THAT THE REFRIGERATION |
| LINES ARE EXISTING WITHIN SPACE AT TIME OF |
| CONSTRUCTION. THERE WILL BE NO MODIFICATIONS ON THESE |
| LINES. THE APPLICATION STATES THIS IS A NEW |
| CONSTRUCTION. REMOVE THIS NOTE OR CORRECT THE |
| APPLICATION. FBC 107.3.5 |
| |
| 9) SHEET M-1.2: REVISE THE DRAWING TO SHOW THE LOCATION |
| OF THE CONDENSING UNIT FOR THE GARAGE APARTMENT. FBC |
| 107.3.5 |
| |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |