2022-10-27 16:45:24 | RESIDENTIAL (R2) BUILDING REVIEW COMMENTS |
| CODE: FBC 7TH EDITION (2020) AND CITY AMENDMENTS. |
| PERMIT #22091328 |
| 1801 S FLAGLER DR # 1704 |
| |
| NOTE: |
| LEVEL 1 ALTERATION. SEC. 602 FBC-EXISTING BUILDING. |
| SEC. 702.6 FBC-EXISTING BUILDING. ALL NEW WORK SHALL |
| COMPLY WITH THE MATERIALS AND METHODS REQUIREMENTS IN |
| THE FLORIDA BUILDING CODE. |
| |
| 1- UNABLE TO VERIFY IF OPENINGS ARE LOCATED ON END OR |
| INTERIOR. SKETCH SUBMITTED ONLY SHOWS AN STAND ALONE |
| APT. PROVIDE SKETCH SHOWING ACTUAL BUILDING DIMENSIONS |
| AND EXACT LOCATION OF OPENINGS. THIS IS MORE CRITICAL |
| FOR END UNITS TO IDENTIFY OPENINGS IN THE END ZONE. |
| SEC. 1609.1 FBC-BUILDING. |
| |
| |
| 2- SPECIFY MULLION SIZE AND FASTENING TO VERIFY |
| COMPLIANCE WITH THE DESIGN PRESSURES. SEC. 1609.1 |
| FBC-BUILDING. CLEARLY MARK ON PRODUCT APPROVAL |
| SUBMITTED |
| NOTE: COORDINATE WITH ITEM #1 ABOVE. |
| |
| 3- SPECIFY SLIDING GLASS DOOR NUMBER OF PANELS/SIZE AND |
| SILL HEIGHT TO VERIFY COMPLIANCE WITH THE DESIGN |
| PRESSURES. SEC. 1609.1 FBC-BUILDING. CLEARLY MARK ON |
| PRODUCT APPROVAL SUBMITTED. |
| NOTE: COORDINATE WITH ITEM #1 ABOVE. |
| |
| 4- SPECIFY WINDOW GLASS TYPE TO VERIFY COMPLIANCE WITH |
| THE DESIGN PRESSURES. SEC. 1609.1 FBC-BUILDING. CLEARLY |
| MARK ON PRODUCT APPROVAL SUBMITTED. |
| NOTE: COORDINATE WITH ITEM #1 ABOVE. |
| |
| 5- WINDOW OPENING CONTROL DEVICES: WINDOW OPENING |
| CONTROL DEVICES ARE REQUIRED WHEN THE WINDOW SILL IS AT |
| A HEIGHT LESS THAN 36 INCHES ABOVE THE FINISHED FLOOR. |
| WINDOW OPENING CONTROL DEVICES NEED TO COMPLY WITH ASTM |
| F2090. |
| CLEARLY SPECIFY IF THERE ARE ANY WINDOWS WHERE THE |
| WINDOW SILL IS LESS THAN 36" ABOVE THE FINISH FLOOR. |
| SEE SEC. 702.4 FBC-EXISTING BUILDING CODE. |
| |
| WHEN RESUBMITTING, A TRANSMITTAL LETTER LISTING THE |
| ORIGINAL REVIEW COMMENT WITH A DESCRIPTION OF WHERE AND |
| HOW THE COMMENT WAS ADDRESSED WILL HELP TO EXPEDITE THE |
| REVIEW PROCESS. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |