Plan Review Notes
Plan Review Notes For Permit 22091292
Permit Number 22091292
Review Stop P
Sequence Number 1
Notes
Date Text
2022-10-17 08:29:321ST PLUMBING REVIEW
  
 V7 FPC - 2020 FLORIDA PLUMBING CODE
 V7 FGC - 2020 FLORIDA FUEL GAS
 V7 FRC - 2020 FLORIDA RESIDENTIAL BUILDING CODE
 V7 FAC - 2020 FLORIDA ACCESSIBILITY CODE
 V7 FEX - 2020 FLORIDA EXISTING BUILDING CODE
 V7 FEC - 2020 FLORIDA ENERGY CONSERVATION
 2021 F.S. - 2021 FLORIDA STATUTES
 2021 F.A.C. - 2021 FLORIDA ADMINISTRATIVE CODE
 2017 WPB AMEND - 2017 WEST PALM BEACH AMENDMENTS TO THE
 FBC CHAPTER 1
  
 THIS PLAN WAS REVIEWED FOR CODE COMPLIANCE AND FAILED
 BY RYAN BROWN WITH THE FOLLOWING COMMENTS.
  
 1. 2020 FPC 403.1.1 - IT APPEARS THAT THE FIXTURES
 PROVIDED DO NOT MEET THE OCCUPANT LOAD SHOWN ON PAGE
 C-1 AT 120 PEOPLE.
  
 2. 2017 WPB AMENDS 107.2.1 - THERE IS A TABLE OF
 CONTENTS PROVIDE ON PAGE C-1 THAT DOES NOT MATCH THE
 PAGES PROVIDED. I DO NOT SEE THE EXISTING FLOOR PLAN.
  
 3. 2020 FPC - 607.1.1 TEMPERATURE LIMITING MEANS - THE
 THERMOSTAT CONTROL ON THE WATER HEATER CANNOT BE THE
 LIMITING DEVICE FOR HOT WATER DELIVERY. PLEASE PROVIDE
 A DETAIL FOR A LIMITING DEVICE FOR THE PURPOSE OF HOT
 WATER DELIVERY. THIS WOULD BE IN ADDITION TO THE
 REQUIREMENTS FOR TEMPERED WATER FOR PUBLIC HANDWASHING
 607.1.2/419.5. AND, THE DEVICE SHALL MEET THE ASSE 1017
 STANDARD AND BE INSTALLED AT THE HOT WATER SOURCE PER
 613.1.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
  