2022-11-14 09:01:18ALTERATION
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) DRAWING C-1 SHOWS BUILDING CONSTRUCTION TYPE II -
 DRAWING A3 SHOWS WOOD FRAMING - PLEASE SHOW WOOD
 FRAMING TO BE FIRE RETARDANT WOOD PER FBC 603.1
 ALLOWABLE MATERIALS.
 COMBUSTIBLE MATERIALS SHALL BE PERMITTED IN BUILDINGS
 OF TYPE I OR II CONSTRUCTION IN THE FOLLOWING
 APPLICATIONS AND IN ACCORDANCE WITH SECTIONS 603.1.1
 THROUGH 603.1.3:
  
 1.FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED IN:
  
 1.1.NONBEARING PARTITIONS WHERE THE REQUIRED
 FIRE-RESISTANCE RATING IS 2 HOURS OR LESS.
  
 2) PLEASE PROVIDE COPIES OF THE PRODUCT APPROVALS SHOWN
 ON DRAWING A-3 FOR THE WINDOWS AND DOORS.
  
 3) PLEASE SHOW THE ACCESSIBLE BAR SEATING - SHOW THE
 FLOOR SPACE, COUNTER HEIGHT, TOE AND KNEE CLEARANCE PER
 FBC ACCESSIBILITY 226
  
 4) PLEASE SHOW THE ACCESSIBLE ROUTE FROM THE ACCESSIBLE
 PARKING SPACE TO THE ENTRY - FBC 206.2.1
  
 5) SIGNED AND SEALED DRAWINGS NEED TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 PROJECTDOX.