2022-11-21 13:44:25POOL BARRIER FENCE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE FENCE DETAILS - TYPE OF FENCE, HEIGHT
 OF FENCE - TO COMPLY WITH POOL BARRIER - FBC R4502.17.1
  
 2) SHOW FENCE GATES TO SWING AWAY FROM THE POOL, BE
 SELF CLOSING AND LATCHING - AND THE OPENING DEVICE PER
 FBC R4501.17.1.8
 ACCESS GATES, WHEN PROVIDED, SHALL BE SELF-CLOSING AND
 SHALL COMPLY WITH THE REQUIREMENTS OF SECTIONS
 R4501.17.1.1 THROUGH R4501.17.1.7 AND SHALL BE EQUIPPED
 WITH A SELF-LATCHING LOCKING DEVICE LOCATED ON THE POOL
 SIDE OF THE GATE. WHERE THE DEVICE RELEASE IS LOCATED
 NO LESS THAN 54 INCHES (1372 MM) FROM THE BOTTOM OF THE
 GATE, THE DEVICE RELEASE MECHANISM MAY BE LOCATED ON
 EITHER SIDE OF THE GATE AND SO PLACED THAT IT CANNOT BE
 REACHED BY A YOUNG CHILD OVER THE TOP OR THROUGH ANY
 OPENING OR GAP FROM THE OUTSIDE. GATES THAT PROVIDE
 ACCESS TO THE SWIMMING POOL MUST OPEN OUTWARD AWAY FROM
 THE POOL. THE GATES AND BARRIER SHALL HAVE NO OPENING
 GREATER THAN 1/2 INCH (12.7 MM) WITHIN 18 INCHES (457
 MM) OF THE RELEASE MECHANISM.