Plan Review Notes
Plan Review Notes For Permit 22091281
Permit Number 22091281
Review Stop B
Sequence Number 2
Notes
Date Text
2023-04-19 08:57:13NEW SFR
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE ADDITIONAL DETAILS FOR THE "THREADED
 BEAM" AT THE REAR PATIO - SHOW ATTACHMENTS TO THE
 STRUCTURE. FBC 107.2.1
  
 2) IN THE PRODUCT APPROVAL FOR THE ROOF TILE - PLEASE
 CIRCLE THE ROOF TILE ATTACHMENTS TO BE USED - IF USING
 ADHESIVE PLEASE PROVIDE THE ADHESIVE PRODUCT APPROVAL.
 FBC WPB 107.2.1.1 FOR ROOF ASSEMBLIES REQUIRED BY THE
 CODE, THE CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE,
 DESCRIBE AND DELINEATE THE TYPE OF ROOFING SYSTEM,
 MATERIALS, FASTENING REQUIREMENTS, FLASHING
 REQUIREMENTS AND WIND RESISTANCE RATING THAT ARE
 REQUIRED TO BE
 INSTALLED
  
 3) PLEASE PRIVIDE THE FLAME CERTIFICATION (ICC
 EVALUATION REPORT) FOR THE FOAM INSULATION AT THE
 BOTTOM OF THE ROOF DECK - R316.3 SURFACE BURNING
 CHARACTERISTICS.
 UNLESS OTHERWISE ALLOWED IN SECTION R316.5, FOAM
 PLASTIC OR FOAM PLASTIC CORES USED AS A COMPONENT IN
 MANUFACTURED ASSEMBLIES USED IN BUILDING CONSTRUCTION
 SHALL HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 75 AND
 SHALL HAVE A SMOKE-DEVELOPED INDEX OF NOT MORE THAN 450
 WHEN TESTED IN THE MAXIMUM THICKNESS AND DENSITY
 INTENDED FOR USE IN ACCORDANCE WITH ASTM E84 OR UL 723.
  
 4) THE SOIL REPORT DOES NOT SHOW AS DIGITALLY SIGNED IN
 ADOBE READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX
 NEED TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED
 IN ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL
 SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A
 SPECIFIC TYPE OF E-SIGNATURE).
  
  