Plan Review Notes For Permit 22091281 |
Permit Number |
22091281 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-19 14:45:00 | NEW SFR | | REVIEWED BY ROGER MCPHERSON | | 561-805-6716 | | [email protected] | | CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1 | | AMENDMENT | | | | CORRECTIONS NEEDED - | | | | 1) ALL PRODUCT APPROVALS NEED TO BE REVIEWED AND MARKED | | APPROVED BY THE BUILDING DESIGNER OF RECORD - FBC WPB | | 107.3.4 | | | | 2) DRAWING S1 "MONO WALL DETAIL" SHOWS ROOFING AS TPO - | | SHOULD IT SAY SHINGLES? | | | | 3) DRAWING S1 "MONO WALL DETAIL" SHOWS FOOTING | | REINFORCEMENT W/3 #7 - FOOTING SCHEDULE DOES NOT MATCH | | - PLEASE CLARIFY | | | | 4) PLEASE SHOW THE ATTIC ACCESS LOCATION AND SIZE PER | | FBC R807.1 | | | | 5) PLEASE SHOW THE EXTERIOR WALL INSULATION TYPE AND | | "R" VALUE ON THE DRAWINGS THAT MATCH THE ENERGY CALCS. | | - FBC WPB 107.2 | | | | 6) PLEASE SHOW THE CEILING INSULATION TYPE ON THE | | DRAWINGS THAT MATCH THE ENERGY CALCS. - FBC WPB 107.2 | | | | 7) PLEASE SHOW THE ATTIC VENTILATION TYPE AND ON CENTER | | SPACING PER FBC R806.1 | | | | 8) PLEASE PROVIDE AN EXTERIOR WINDOW FLASHING DETAIL | | PER FBC R703.4 | | | | 9) THE ARCHITECTURAL, STRUCTURAL DRAWINGS AND THE SOIL | | REPORT DOES NOT SHOW AS DIGITALLY SIGNED IN ADOBE | | READER - SIGNED AND SEALED DRAWINGS IN PROJECTDOX NEED | | TO BE DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN | | ELECTRONIC PLAN REVIEW. (A CERTIFICATE-BASED DIGITAL | | SIGNATURE (OFTEN JUST CALLED A DIGITAL SIGNATURE) IS A | | SPECIFIC TYPE OF E-SIGNATURE). | | | | |
|