2022-11-01 13:34:201ST REVIEW FMC
 PERMIT: 22100465
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE REVISE THE ADDRESS ON THE DRAWINGS TO THE
 CORRECTED ADDRESS: 206 S. OLIVE.
  
 2) PROVIDE A SITE PLAN FOR THIS BUILDING THAT INCLUDES
 THE PROPERTY LOT LINES.
  
 3) PROVIDE A DETAIL OF THE GREASE DUCT AND HEAT PIPE
 THAT IS EXISTING INCLUDING THE TERMINATION LOCATIONS.
 FBC107.3.5
  
 4) PLEASE ADD A NOTE ON THE MECHANICAL DRAWING STATING
 THAT THE KITCHEN HOOD, GREASE DUCT AND WALK-IN COOLERS
 WILL REQUIRE SEPARATE PERMIT APPLICATIONS AND
 MECHANICAL REVIEWS AS THEY WILL NOT BE REVIEWED UNDER
 THIS PERMIT.
  
 5) PROVIDE DETAILS FOR THE SMOKER. FMC 906
  
 6) THE COOKING EQUIPMENT INCLUDING THE SMOKER SHALL BE
 LISTED AND LABELED FOR INDOOR USE. FMC 917.1
  
 7) PROVIDE DETAILS AS TO WHAT WILL BE UNDER THE HEAT
 HOOD. SHEET 4.0M INDICATES EXISTING WELDED DUCTWORK TO
 ROOF. SHEET 1.1A DEMO DRAWING DOES NOT SHOW THIS DUCT
 WORK AS EXISTING. PLEASE CORRECT THE STATEMENT ON 4.0M
 TO INDICATE THIS TO BE A NEW HEAT DUCT. FBC 107.3.5
  
 8) PLEASE CORRECT THE OUTDOOR AIR CALCULATIONS. DINING
 ROOM OUTDOOR AIR RATE FOR CFM/FT2 SHOULD BE CALCULATED
 AT .18 NOT .12. THIS WOULD MAKE THE TOTAL OUTDOOR AIR
 FOR THIS AREA TO BE 261 CFM???S. FMC TABLE 403.3.1.1
  
 9) THE OUTDOOR AIR CALCULATIONS FOR THE KITCHEN SHOULD
 SHOW 79 CFM???S OF OUTDOOR AIR REQUIRED WITH 197
 CFM???S OF REQUIRED EXHAUST FOR THIS KITCHEN. FMC TABLE
 403.3.1.1
  
 10) PLEASE PROVIDE THE AIR BALANCE DESIGN FOR THIS
 TENANT SPACE. FMC 508.1.2
  
 11) THE NEW FLOOR PLAN ON 1.1A INDICATES A NEW WALL
 OPENING INTO THE TENANT SPACE BESIDE OF THIS TENANT.
 PROVIDE THE OCCUPANCY AND USE OF SPACE FOR THIS TENANT
 SPACE ALONG WITH THE MECHANICAL SYSTEM SIZING. FMC
 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS