Plan Review Notes
Plan Review Notes For Permit 22091246
Permit Number 22091246
Review Stop P
Sequence Number 2
Notes
Date Text
2022-12-09 14:24:072ND REVIEW FBC-2020 PLUMBING
 PERMIT- 22091246
 12/9/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED. COMMENT #2 COPIED BELOW
 FROM THE 1ST REVIEW WAS NOT ADDRESSED. PLEASE COMPLY BY
 EITHER INSTALLING A RECIRCULATION LINE WITH LOOPS TO
 THE LAVATORIES, OR POINT OF USE WATER HEATERS.
  
 2) P-1: THE 1/2--INCH HW SUPPLY PIPES TO THE NEW
 LAVATORIES ARE EXCEEDING THEIR MAXIMUM ALLOWABLE 2-FT.
 LENGTHS PER TABLE C404.5.1 FBC EC.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  
 CHRISTOPHER L. COLE
 MECHANICAL/PLUMBING PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  