2022-10-26 12:57:111ST REVIEW FBC-2020 PLUMBING
 PERMIT- 22091246
 10/26/22
  
 CODES IN EFFECT:
 FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020
 FBC ACC- FLORIDA ACCESSIBILITY CODE 7TH EDITION 2020
 FBC EC- FLORIDA ENERGY CONSERVATION CODE 7TH EDITION
 2020
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET P-1: THE MEN'S AND WOMEN'S TOILET ROOM DOORS
 SHALL NOT SWING INTO THE CLEAR FLOOR SPACES FOR THE
 LAVATORIES- SEC. 603.2.3 FBC ACC. PLEASE SEE EXCEPTION
 2 FOR ADDITIONAL INFORMATION.
  
 2) P-1: THE 1/2--INCH HW SUPPLY PIPES TO THE NEW
 LAVATORIES ARE EXCEEDING THEIR MAXIMUM ALLOWABLE 2-FT.
 LENGTHS PER TABLE C404.5.1 FBC EC.
  
 3) P-1: PLEASE CORRECT WATER RISER NOTE # SPECIFYING
 5/8-INCH HW PIPE INSULATION. REFER TO TABLE C403.2.10
 FBC EC- MINIMUM 1-INCH THICK INSULATION REQUIRED.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM.
  