2022-10-04 09:50:10 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS: MONDAY - FRIDAY 7:00 AM TO 3:00 PM |
| PHONE (561) 805-6656 |
| EMAIL: [email protected] |
| |
| 1ST REVIEW: FBC 2020 7TH EDITION |
| FBC = FLORIDA BUILDING CODE, 7TH EDITION (2020) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| TO RESUBMIT, YOU CAN EITHER DROP OFF YOUR SUBMITTAL AT |
| CITY HALL, OR UPLOAD CORRECTIONS TO PROJECTDOX. |
| |
| 1. SUBMITTED PRODUCT APPROVAL FL2533-R26 HAS BEEN |
| REVISED TO FL2533-R28. PLEASE PROVIDE THE FOLLOWING: |
| COVER PAGE, EVALUATION REPORT PAGES 1-5 AND |
| INSTALLATION INSTRUCTIONS FOR SYSTEM USED. ALL |
| APPLICABLE DETAILS AND ATTACHMENTS MUST BE CLEARLY |
| IDENTIFIED ON THE PRODUCT APPROVAL DRAWINGS. DETAILS |
| AND ATTACHMENTS NOT SPECIFICALLY COVERED IN PRODUCT |
| APPROVALS WILL NEED SITE-SPECIFIC ENGINEERING. AS PER |
| RULE 61G20-3. |
| 2. FBC R 301 FAC9N-3 SUBMITTED FLORIDA DBPR PRODUCT |
| APPROVAL FL2533-R26 SYSTEM NO. W-72 DOES NOT MEET THE |
| MINIMUM ZONE 3 DESIGN PRESSURE REQUIREMENT OF -108.17 |
| FOR EXPOSURE CATEGORY C AREAS. PROVIDE SYSTEM THAT |
| MEETS OR EXCEEDS ALL DESIGN PRESSURE REQUIREMENTS FOR |
| EXPOSURE CATEGORY C/PROVIDE SIGNED AND SEALED |
| ENGINEERED NAILING CALCULATIONS WITH AN APPROVED |
| SYSTEM. |
| 3. FBC B 107.1 IF THE DESIGN PROFESSIONAL IS AN |
| ARCHITECT, INTERIOR DESIGNER, OR ENGINEER LEGALLY |
| REGISTERED UNDER THE LAWS OF THE STATE OF FLORIDA |
| REGULATING THE PRACTICE OF ARCHITECTURE OR INTERIOR |
| DESIGN AS PROVIDED FOR IN CHAPTER 481, FLORIDA |
| STATUTES, PART I, OR LANDSCAPE ARCHITECTURE AS PROVIDED |
| FOR IN CHAPTER 481, FLORIDA STATUTES, PART II, OR |
| ENGINEERING AS PROVIDED FOR IN CHAPTER 471, FLORIDA |
| STATUTES, THEN HE OR SHE SHALL AFFIX HIS OR HER |
| OFFICIAL SEAL TO SAID DRAWINGS, SPECIFICATIONS AND |
| ACCOMPANYING DATA, AS REQUIRED BY FLORIDA STATUTE. |
| SUBMITTED ROOF DRAIN PLAN MUST BE SIGNED & SEALED BY |
| THE ARCHITECT. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| |