2022-12-22 12:36:30 | 1ST REVIEW FBC-2020 RES. PLUMBING | | PERMIT- 22091107 | | 12/22/2022 | | | | CODES IN EFFECT: | | FBC RES- FLORIDA RESIDENTIAL BUILDING CODE 7TH EDITION | | 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) THE SUBMITTED MANUFACTURER???S SPECIFICATIONS FOR | | THE PUMP AND LIGHT HAVE BEEN LOCKED OUT BECAUSE THEY | | BEAR PERMIT APPROVAL STAMPS FROM THE CITY OF PORT SAINT | | LUCIE- SEC. 107.2.1 WPB. THE PUMP SPECS SUBMITTED ARE | | NOT FOR THE PUMP SPECIFIED IN THE EQUIPMENT SCHEDULE ON | | P-4. PLEASE SUBMIT NEW SPECIFICATIONS SHEETS BASED ON | | THE MAKES AND MODELS SHOWN IN THE SCHEDULE. | | | | 2) MANUFACTURER???S SPECIFICATIONS HAVE BEEN SUBMITTED | | FOR AN AQUACAL HEAT PUMP/CHILLER AND INTELLICHLOR SALT | | GENERATOR. PLEASE ADD THESE ITEMS TO THE EQUIPMENT | | SPECS ON P-4, AND TO THE PIPING SCHEMATIC ON P-3- SEC. | | 107.2.1 WPB. | | | | 3) P-3: PROVIDE TDH CALCULATIONS AND THE POOL PUMP | | CURVE MARKED UP TO SHOW THE DESIGN FLOW RATE AND THE | | HEAD LOSS- SECS. 4.4.9, 4.4.9.1 ANSI/APSP/ICC 7. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|