2023-01-03 09:06:532ND REVIEW FMC
 PERMIT: 22091089
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M-130: OUTDOOR AIR CALCULATIONS FOR AHU-1; IT
 APPEARS THAT THE LOBBIES/PREFUNCTION CALCULATIONS IS
 USING THE WRONG OCCUPANCY DENSITY. THE OCCUPANCY
 DENSITY FOR LOBBIES/PREFUNCTION SHOULD BE 30 AND NOT
 10. THIS HAS MADE THE OUTDOOR AIR CALCULATION TOO LOW
 FOR THE SPACE. PLEASE CHECK THE NUMBERS AND MAKE THE
 REQUIRED CORRECTIONS. FMC 403.3.1.1
  
 2) PLEASE PROVIDE THE AHU SYSTEM VENTILATION RATE
 COMPLETE CALCULATION FOR EACH AHU. FMC 403.3.1.1
  
 3) PROVIDE THE REQUIRED EXHAUST FOR THE COPY/PRINT
 AREA. FMC TABLE 403.3.1.1
  
 4) SHEET M-510: PLEASE SHOW HOW OUTDOOR AIR WILL BE
 INTRODUCED FOR THE 2ND FLOOR AHU-2. FBC 107.3.5
  
 5) PLEASE REFERENCE THE SHEET AND NOTE THAT STATES THE
 BATHROOM EXHAUST FANS ARE CONTINUOUSLY OPERATED, SHEET
 M-120 DOES NOT MENTION THE FANS ARE CONTINUOUSLY
 OPERATED. CONTROL INTERLOCKS DOES LIST SCHEDULE. FMC
 TABLE 403.3.1.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  