2023-01-03 09:06:53 | 2ND REVIEW FMC |
| PERMIT: 22091089 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-130: OUTDOOR AIR CALCULATIONS FOR AHU-1; IT |
| APPEARS THAT THE LOBBIES/PREFUNCTION CALCULATIONS IS |
| USING THE WRONG OCCUPANCY DENSITY. THE OCCUPANCY |
| DENSITY FOR LOBBIES/PREFUNCTION SHOULD BE 30 AND NOT |
| 10. THIS HAS MADE THE OUTDOOR AIR CALCULATION TOO LOW |
| FOR THE SPACE. PLEASE CHECK THE NUMBERS AND MAKE THE |
| REQUIRED CORRECTIONS. FMC 403.3.1.1 |
| |
| 2) PLEASE PROVIDE THE AHU SYSTEM VENTILATION RATE |
| COMPLETE CALCULATION FOR EACH AHU. FMC 403.3.1.1 |
| |
| 3) PROVIDE THE REQUIRED EXHAUST FOR THE COPY/PRINT |
| AREA. FMC TABLE 403.3.1.1 |
| |
| 4) SHEET M-510: PLEASE SHOW HOW OUTDOOR AIR WILL BE |
| INTRODUCED FOR THE 2ND FLOOR AHU-2. FBC 107.3.5 |
| |
| 5) PLEASE REFERENCE THE SHEET AND NOTE THAT STATES THE |
| BATHROOM EXHAUST FANS ARE CONTINUOUSLY OPERATED, SHEET |
| M-120 DOES NOT MENTION THE FANS ARE CONTINUOUSLY |
| OPERATED. CONTROL INTERLOCKS DOES LIST SCHEDULE. FMC |
| TABLE 403.3.1.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |