Plan Review Notes
Plan Review Notes For Permit 22091089
Permit Number 22091089
Review Stop Z
Sequence Number 1
Notes
Date Text
2022-11-28 14:56:19FAILED
  
 1) PROVIDE A SURVEY OF THE AREA SUBJECT TO THIS PERMIT.
 THE SURVEY, OR A SITE PLAN, MUST SHOW THE SETBACK
 DIMENSIONS FROM THE EXISTING SANCTUARY BUILDING AND THE
 WEST PROPERTY LINE.
  
 2) THE FLOOR PLAN OF THE BUILDING DOES NOT MATCH THE
 BUILDING APPROVED THROUGH THE SITE PLAN PROCESS. A NEW
 DOOR HAS BEEN ADDED ON THE EAST SIDE OF THE BUILDING
 THAT DIRECTLY CONFLICTS WITH THE APPROVED LANDSCAPE.
 ALL THE PLANS MUST SHOW ACCURATE, CONSISTENT, CODE
 COMPLIANT CONDITIONS. THE NEW BUILDING FLOOR PLAN IS
 NOT SHOWN ON THE PLUMBING SITE PLAN, THE MECHANICAL
 SITE PLAN, AND THE ELECTRICAL SITE PLAN.
  
 3) WHILE THE PARKING, LANDSCAPE, DUMPSTER ENCLOSURE AND
 CHILLER PLANT ARE NOT PART OF THE REVIEW OF THIS
 BUILDING PERMIT, THE PLANS SHOW CHANGES TO THESE
 FEATURES FROM WHAT WAS APPROVED AS PART OF THE SITE
 PLAN APPROVAL. A MINOR SITE PLAN AMENDMENT MUST BE
 SUBMITTED TO THE PLANNING DIVISION AND APPROVED, PRIOR
 TO ZONING APPROVAL OF THIS PERMIT. THE SITE PLAN
 AMENDMENT REVIEW WILL INCLUDE REVIEWS BY THE CITY'S
 SANITATION AND LANDSCAPE REVIEWERS TO VERIFY THAT ALL
 CODE PROVISIONS STILL COMPLY.
  
 4) THE SITE PLAN APPROVAL, INCLUDING THE PALM BEACH
 COUNTY TRAFFIC APPROVAL, ARE FOR A 17,733 SQUARE FOOT
 BUILDING. THE PERMIT SHOWS A 17,740 SQUARE FOOT
 BUILDING. THE MINOR SITE PLAN AMENDMENT MUST REFLECT
 THIS INCREASE IN SQUARE FOOTAGE, TO INCLUDE AN UPDATED
 PALM BEACH COUNTY TRAFFIC APPROVAL.
  
 5) THE SECOND LEVEL FLOOR PLAN SHOWS THE MAJORITY OF
 THE SQUARE FOOTAGE AS OFFICE SPACE, WHICH IS NOT WHAT
 WAS APPROVED AS PART OF THE SITE PLAN REVIEW, WHICH
 CLASSIFIED THE ENTIRE BUILDING AS ASSEMBLY SPACE FOR
 THE PROVISION OF PARKING. THE MINOR SITE PLAN AMENDMENT
 MUST ACCURATELY REFLECT THE PARKING REQUIREMENTS FOR
 THE OFFICE SQUARE FOOTAGE AND VERIFY THAT THE SITE
 MEETS THE MINIMUM PARKING REQUIREMENTS.
  
 6) THE DIMENSIONS ON THE FLOOR PLAN DO NOT MATCH THE
 DIMENSIONS ON THE SITE PLAN. THIS MUST BE UPDATED AS
 PART OF THE MINOR SITE PLAN AMENDMENT.
  
 7) SEPARATE PERMITS WITH PLANS ARE REQUIRED FOR THE
 FOLLOWING:
  
 A. SITE LIGHTING.
 B. DUMPSTER ENCLOSURE.
 C. CHILLER PLANT. NOTE: THE CHILLER ENCLOSURE MUST
 SCREEN THE FULL HEIGHT OF THE CHILLER EQUIPMENT.
 D. NEW GENERATOR.
 E. BICYCLE RACKS.
  
 8) PRIOR TO THE REMOVAL OR RELOCATION OF ANY TREES ON
 THE PROPERTY, A TREE ALTERATION PERMIT SHALL BE
 SUBMITTED, REVIEWED AND APPROVED BY THE DEVELOPMENT
 SERVICES DEPARTMENT, PLANNING DIVISION.
  
 CONTACT ERIC SCHNEIDER @ 562-822-1446
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved