2022-10-31 12:32:32 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2020 7TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1 |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020 |
| 7TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| 22091089 8350 OKEECHOBEE BLVD |
| |
| 1ST REVIEW: DENIED |
| THE BACKFLOW PERMIT IS REQUIRED TO BE SUBMITTED PRIOR |
| TO ISSUANCE OF THE PRIMARY PERMIT (AS APPLICABLE). YOU |
| CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF |
| YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A |
| COMPLETED PERMIT APPLICATION TO [email protected] |
| . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD |
| PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE |
| DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE |
| RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE |
| SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED, |
| PLEASE NOTIFY ME AT [email protected] AND CC SAMANTHA |
| HILL, CHIEF PLANS EXAMINER AT [email protected] AND RYAN |
| BROWN, CHIEF PLUMBING INSPECTOR AT [email protected] VIA |
| EMAIL WITH THE PERMIT NUMBER(S) |
| |
| 1. RM 205 BREAKROOM SINK COUNTERTOP IS 36 INCHES FROM |
| FLOOR AS WELL AS RM 103, 104, 105. 106, 110, 111, 229 |
| AND 230. ALL HAVE DESIGNATED CLEAR FLOOR SPACE |
| INDICATING ACCESSIBILITY. A412/01 DETAIL INDICATES SINK |
| COUNTERTOP IS 36 INCHES FROM FLOOR. PER FAC 603.3, |
| ACCESSIBLE LAVATORIES AND SINKS SHALL BE INSTALLED WITH |
| THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE |
| 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR |
| GROUND. |
| |
| 2. DESIGNATE ACCESSIBLE URINAL AND SHOW CLEAR FLOOR |
| SPACE. FAC 605.3 |
| |
| 3. IT HAS BEEN AND IS THE POSITION TAKEN BY THIS |
| DEPARTMENT THAT PAINTED DRYWALL, EVEN WHERE COATED WITH |
| HIGHLY DURABLE PAINTS SUCH AS EPOXY, DOES NOT MEET THE |
| INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS USED |
| FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS |
| REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS, |
| LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS |
| STEEL. |
| ***A) HARD FINISH REQUIRED ON NORTH (SIDE) WALL |
| ADJACENT TO MEN/WOMEN ACCESSIBLE WATER CLOSET TO A |
| HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR. FBC PL |
| 310.3, FBC 1210.2.2 |
| ***B) ALL INDIVIDUAL RESTROOMS SHALL HAVE SMOOTH HARD |
| FINISH SIDEWALL ADJACENT TO WATER CLOSET TO A HEIGHT OF |
| NOT LESS THAN 4 FEET ABOVE THE FLOOR. FBC PL 310.3, FBC |
| 1210.2.2 |
| ***C) CUSTODIAL RM-231 REQUIRES SMOOTH HARD FINISH WALL |
| WITHIN 2 FEET OF MOP SINK TO A HEIGHT OF NOT LESS THAN |
| 4 FEET ABOVE THE FLOOR. FBC PL 310.3, FBC 1210.2.2 |
| |
| 4. P-029 PLUMBING SITE PLAN REFERS TO CIVIL DRAWINGS. |
| PER WPB FBC 107.2.1, PLEASE PROVIDE WATER, SEWER AND |
| DRAINAGE CIVIL DRAWINGS |
| |
| 5.P-400: PROVIDE VENT FOR URINALS. FBC PL 909.1 |
| |
| 6. P-400: 2 INCH SANITARY/SOIL STACK TO SECOND FLOOR |
| RESTROOMS IS NOT COMPLIANT. FBC PL 704.2, 710.1. PLEASE |
| CLARIFY AND RECONCILE WITH P-100 AND P-110. |
| |
| 7. P-400: PROVIDE P-TRAPS FOR FLOOR DRAINS. FBC PL |
| 1002.1 |
| |
| 8. P-400/P-100: PLEASE CONTINUE HORIZONTAL WASTE BRANCH |
| FROM MOST UPSTREAM WATER CLOSET OF FIRST FLOOR BATHROOM |
| BATTERY TO THE UPSTREAM DRY VENT FULL SIZE 4 INCH TO |
| COMPLY WITH FBC PL 914.3. |
| |
| 9. P-400/P-110: PLEASE CONTINUE HORIZONTAL WASTE BRANCH |
| FROM MOST UPSTREAM WATER CLOSET OF SECOND FLOOR |
| BATHROOM BATTERY TO THE UPSTREAM DRY VENT FULL SIZE 4 |
| INCH TO COMPLY WITH FBC PL 914.3. |
| |
| 10. PROVIDE CALCULATIONS FOR SIZING OF WATER PIPE. WPB |
| FBC 107.3.5.1.3(3) |
| |
| 11. P-510 WATER HEATER DETAIL; PROVIDE VACUUM RELIEF |
| VALVE IN COLD WATER FEED. FBC PL 504.2 |
| |
| 12. PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; COMPLY |
| WITH FBC EC TABLE C404.2 |
| |
| 13. PLAN SHEETS P-200, P-210 AND P-410: REFER TO FBC EC |
| TABLE C404.5.1; THE 1/2 -INCH HOT WATER PIPE TO THE |
| PUBLIC LAVATORIES SHALL NOT EXCEED 2 FEET FROM THE HOT |
| WATER SOURCE (HOT WATER RECIRCULATING SYSTEM). |
| |
| 14. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL |
| WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE |
| SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5." |
| |
| 15. REGARDING P-010 PLUMBING FIXTURE SCHEDULE, REMARKS |
| FOR L-1 AND L-2 STATE "PLUMBING CONTRACTOR TO CONNECT |
| COLD WATER TO BOTH HOT WATER AND COLD WATER CONNECTIONS |
| ON THE FAUCET"; PLAN SHEETS P-200, P-210 AND P-410 SHOW |
| HOT WATER CONNECTED TO FIXTURE. PER WPB FBC 107.2.1, |
| PLEASE CLARIFY AND RECONCILE. |
| IF HOT WATER IS TO BE SUPPLIED TO PUBLIC LAVATORIES |
| THEN PER FBC PL 419.5, PROVIDE AN APPROVED |
| WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE |
| 1070 OR CSA B125.3. |
| |
| 16. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC |
| FOR EACH SYSTEM TO INCLUDE PIPE, VALVES, FITTINGS AND |
| JOINTS. COMPLY WITH FBC PL CHAPTERS 3, 6, 7, 9 AND 11. |
| |
| 17. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL |
| FOR THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING: |
| ***WATER HEATER |
| ***BACKFLOW PREVENTER DEVICES |
| ***THERMOSTATIC MIXING VALVES |
| ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC |
| 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN |
| ACCORDANCE WITH SECTION WPB FBC 107.3.4.1. |
| DEFERRED SUBMITTALS SHALL BE LISTED ON THE PLANS |
| |
| 18. PER WPB FBC 107.3.5.1.3(7), PLEASE SHOW ON P-420, |
| THE LOCATION(S) OF REQUIRED BACKWATER VALVE(S). FBC PL |
| 1101.9 AND SECTION 714. |
| |
| 19. PER WPB FBC 107.3.5.1.3(4), PROVIDE SANITARY SIZING |
| CALCULATIONS. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| |