Plan Review Notes
Plan Review Notes For Permit 22091089
Permit Number 22091089
Review Stop P
Sequence Number 1
Notes
Date Text
2022-10-31 12:32:32CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2020 7TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2020
 7TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2020 7TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2020 7TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2020 7TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 22091089 8350 OKEECHOBEE BLVD
  
 1ST REVIEW: DENIED
 THE BACKFLOW PERMIT IS REQUIRED TO BE SUBMITTED PRIOR
 TO ISSUANCE OF THE PRIMARY PERMIT (AS APPLICABLE). YOU
 CAN SUBMIT AN APPLICATION "TBD" (TO BE DETERMINED) IF
 YOU DO NOT HAVE A CONTRACTOR SELECTED BY EMAILING A
 COMPLETED PERMIT APPLICATION TO [email protected]
 . YOU WILL RECEIVE INSTRUCTIONS TO PAY FEES AND UPLOAD
 PLANS. YOU MAY UPLOAD PLANS AND PAY FEES AT A FUTURE
 DATE, BUT THE APPLICATION IS REQUIRED AT THIS TIME. WE
 RECOMMEND THAT YOU PAY FEES AND UPLOAD PLANS AT THE
 SAME TIME. AFTER YOU HAVE THE PERMIT(S) GENERATED,
 PLEASE NOTIFY ME AT [email protected] AND CC SAMANTHA
 HILL, CHIEF PLANS EXAMINER AT [email protected] AND RYAN
 BROWN, CHIEF PLUMBING INSPECTOR AT [email protected] VIA
 EMAIL WITH THE PERMIT NUMBER(S)
  
 1. RM 205 BREAKROOM SINK COUNTERTOP IS 36 INCHES FROM
 FLOOR AS WELL AS RM 103, 104, 105. 106, 110, 111, 229
 AND 230. ALL HAVE DESIGNATED CLEAR FLOOR SPACE
 INDICATING ACCESSIBILITY. A412/01 DETAIL INDICATES SINK
 COUNTERTOP IS 36 INCHES FROM FLOOR. PER FAC 603.3,
 ACCESSIBLE LAVATORIES AND SINKS SHALL BE INSTALLED WITH
 THE FRONT OF THE HIGHER OF THE RIM OR COUNTER SURFACE
 34 INCHES (865 MM) MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 2. DESIGNATE ACCESSIBLE URINAL AND SHOW CLEAR FLOOR
 SPACE. FAC 605.3
  
 3. IT HAS BEEN AND IS THE POSITION TAKEN BY THIS
 DEPARTMENT THAT PAINTED DRYWALL, EVEN WHERE COATED WITH
 HIGHLY DURABLE PAINTS SUCH AS EPOXY, DOES NOT MEET THE
 INTENT OF SECTION 1210.2.2. THE TYPICAL MATERIALS USED
 FOR THIS APPLICATION ARE CERAMIC TILE, FIBERGLASS
 REINFORCED PLASTIC (FRP) PANELS, PHENOLIC PANELS,
 LAMINATED PLASTIC PANELS, PAINTED STEEL AND STAINLESS
 STEEL.
 ***A) HARD FINISH REQUIRED ON NORTH (SIDE) WALL
 ADJACENT TO MEN/WOMEN ACCESSIBLE WATER CLOSET TO A
 HEIGHT OF NOT LESS THAN 4 FEET ABOVE THE FLOOR. FBC PL
 310.3, FBC 1210.2.2
 ***B) ALL INDIVIDUAL RESTROOMS SHALL HAVE SMOOTH HARD
 FINISH SIDEWALL ADJACENT TO WATER CLOSET TO A HEIGHT OF
 NOT LESS THAN 4 FEET ABOVE THE FLOOR. FBC PL 310.3, FBC
 1210.2.2
 ***C) CUSTODIAL RM-231 REQUIRES SMOOTH HARD FINISH WALL
 WITHIN 2 FEET OF MOP SINK TO A HEIGHT OF NOT LESS THAN
 4 FEET ABOVE THE FLOOR. FBC PL 310.3, FBC 1210.2.2
  
 4. P-029 PLUMBING SITE PLAN REFERS TO CIVIL DRAWINGS.
 PER WPB FBC 107.2.1, PLEASE PROVIDE WATER, SEWER AND
 DRAINAGE CIVIL DRAWINGS
  
 5.P-400: PROVIDE VENT FOR URINALS. FBC PL 909.1
  
 6. P-400: 2 INCH SANITARY/SOIL STACK TO SECOND FLOOR
 RESTROOMS IS NOT COMPLIANT. FBC PL 704.2, 710.1. PLEASE
 CLARIFY AND RECONCILE WITH P-100 AND P-110.
  
 7. P-400: PROVIDE P-TRAPS FOR FLOOR DRAINS. FBC PL
 1002.1
  
 8. P-400/P-100: PLEASE CONTINUE HORIZONTAL WASTE BRANCH
 FROM MOST UPSTREAM WATER CLOSET OF FIRST FLOOR BATHROOM
 BATTERY TO THE UPSTREAM DRY VENT FULL SIZE 4 INCH TO
 COMPLY WITH FBC PL 914.3.
  
 9. P-400/P-110: PLEASE CONTINUE HORIZONTAL WASTE BRANCH
 FROM MOST UPSTREAM WATER CLOSET OF SECOND FLOOR
 BATHROOM BATTERY TO THE UPSTREAM DRY VENT FULL SIZE 4
 INCH TO COMPLY WITH FBC PL 914.3.
  
 10. PROVIDE CALCULATIONS FOR SIZING OF WATER PIPE. WPB
 FBC 107.3.5.1.3(3)
  
 11. P-510 WATER HEATER DETAIL; PROVIDE VACUUM RELIEF
 VALVE IN COLD WATER FEED. FBC PL 504.2
  
 12. PROVIDE ENERGY EFFICIENCY FOR WATER HEATER; COMPLY
 WITH FBC EC TABLE C404.2
  
 13. PLAN SHEETS P-200, P-210 AND P-410: REFER TO FBC EC
 TABLE C404.5.1; THE 1/2 -INCH HOT WATER PIPE TO THE
 PUBLIC LAVATORIES SHALL NOT EXCEED 2 FEET FROM THE HOT
 WATER SOURCE (HOT WATER RECIRCULATING SYSTEM).
  
 14. PER WPB FBC 107.2.1, PROVIDE PIPE HANGER DETAIL
 WITH A NOTE STATING, "HORIZONTAL PIPE SHALL BE
 SUPPORTED IN ACCORDANCE WITH FBC PL TABLE 308.5."
  
 15. REGARDING P-010 PLUMBING FIXTURE SCHEDULE, REMARKS
 FOR L-1 AND L-2 STATE "PLUMBING CONTRACTOR TO CONNECT
 COLD WATER TO BOTH HOT WATER AND COLD WATER CONNECTIONS
 ON THE FAUCET"; PLAN SHEETS P-200, P-210 AND P-410 SHOW
 HOT WATER CONNECTED TO FIXTURE. PER WPB FBC 107.2.1,
 PLEASE CLARIFY AND RECONCILE.
 IF HOT WATER IS TO BE SUPPLIED TO PUBLIC LAVATORIES
 THEN PER FBC PL 419.5, PROVIDE AN APPROVED
 WATER-TEMPERATURE LIMITING DEVICE THAT CONFORMS TO ASSE
 1070 OR CSA B125.3.
  
 16. PER WPB FBC 107.2.1, PROVIDE PIPING MATERIAL SPEC
 FOR EACH SYSTEM TO INCLUDE PIPE, VALVES, FITTINGS AND
 JOINTS. COMPLY WITH FBC PL CHAPTERS 3, 6, 7, 9 AND 11.
  
 17. MANUFACTURER'S SPECIFICATION/INSTALLATION MANUAL
 FOR THE FOLLOWING SHALL BE PROVIDED FOR THE FOLLOWING:
 ***WATER HEATER
 ***BACKFLOW PREVENTER DEVICES
 ***THERMOSTATIC MIXING VALVES
 ALL SUBMITTALS SHALL BE APPROVED AND STAMP BY THE
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE- WPB FBC
 107.2.1, 107.3.4. SUBMITTALS MAY BE DEFERRED IN
 ACCORDANCE WITH SECTION WPB FBC 107.3.4.1.
 DEFERRED SUBMITTALS SHALL BE LISTED ON THE PLANS
  
 18. PER WPB FBC 107.3.5.1.3(7), PLEASE SHOW ON P-420,
 THE LOCATION(S) OF REQUIRED BACKWATER VALVE(S). FBC PL
 1101.9 AND SECTION 714.
  
 19. PER WPB FBC 107.3.5.1.3(4), PROVIDE SANITARY SIZING
 CALCULATIONS.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS. ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER PX928
 PLUMBING INSPECTOR BN2148
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 MOBILE 561-246-0882
  