2022-11-07 13:06:191ST REVIEW FMC
 PERMIT: 22091089
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON
 THE OCCUPANCY CLASSIFICATIONS FOUND IN FMC TABLE
 403.3.1.1. I CANNOT COMPARE THE SUBMITTED CALCULATIONS
 WITH TABLE 403.3.1.1. I CANNOT COMPARE THE CALCULATIONS
 UNTIL YOU PROVIDE ME WITH OCCUPANCIES IDENTIFIED FROM
 TABLE 403.3.1.1. FMC 403.3.1.1
  
 2) THE BATHROOM EXHAUST MUST MEET THE MINIMUM CFM???S
 BASED ON FMC TABLE 403.3.1.1. PLEASE SHOW THAT THE
 CFM???S WILL MEET THE 70 CFM???S PER WATER CLOSET OR
 URINAL. EXAMPLE: EF2-2 SHOULD HAVE A MINIMUM OF 420
 CFM???S OF EXHAUST. 6 X 70 = 420. EF-1-5 SHOULD HAVE A
 MINIMUM OF 490 CFM???S.
  
 3) SHEET M-300: NEW WORK NOTE 11 IS REFERENCING A
 EF1-6, THE IS NO EF-1-6 IN THE FAN SCHEDULE ON SHEET
 M-120. PLEASE CORRECT NEW WORK KEYNOTE 11. FBC 107.3.5
  
 4) REVISE THE MECHANICAL DRAWINGS TO SHOW THE DUCT
 DETECTORS IN THE SUPPLY SIDE OF THE DUCTWORK. FMC 606.1
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  