Date |
Text |
2022-11-07 13:06:19 | 1ST REVIEW FMC |
| PERMIT: 22091089 |
| |
| CODES IN EFFECT: 2020 |
| |
| FBC- FLORIDA BUILDING CODE |
| FMC- FLORIDA MECHANICAL CODE |
| FEC- FLORIDA ENERGY CONSERVATION |
| FGC- FLORIDA FUEL GAS |
| FEX- FLORIDA EXISTING BUILDING CODE |
| FRC- FLORIDA RESIDENTIAL BUILDING CODE |
| F.S.- FLORIDA STATUTES |
| FAC- FLORIDA ACCESSIBILITY CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE THE OUTDOOR AIR CALCULATIONS BASED ON |
| THE OCCUPANCY CLASSIFICATIONS FOUND IN FMC TABLE |
| 403.3.1.1. I CANNOT COMPARE THE SUBMITTED CALCULATIONS |
| WITH TABLE 403.3.1.1. I CANNOT COMPARE THE CALCULATIONS |
| UNTIL YOU PROVIDE ME WITH OCCUPANCIES IDENTIFIED FROM |
| TABLE 403.3.1.1. FMC 403.3.1.1 |
| |
| 2) THE BATHROOM EXHAUST MUST MEET THE MINIMUM CFM???S |
| BASED ON FMC TABLE 403.3.1.1. PLEASE SHOW THAT THE |
| CFM???S WILL MEET THE 70 CFM???S PER WATER CLOSET OR |
| URINAL. EXAMPLE: EF2-2 SHOULD HAVE A MINIMUM OF 420 |
| CFM???S OF EXHAUST. 6 X 70 = 420. EF-1-5 SHOULD HAVE A |
| MINIMUM OF 490 CFM???S. |
| |
| 3) SHEET M-300: NEW WORK NOTE 11 IS REFERENCING A |
| EF1-6, THE IS NO EF-1-6 IN THE FAN SCHEDULE ON SHEET |
| M-120. PLEASE CORRECT NEW WORK KEYNOTE 11. FBC 107.3.5 |
| |
| 4) REVISE THE MECHANICAL DRAWINGS TO SHOW THE DUCT |
| DETECTORS IN THE SUPPLY SIDE OF THE DUCTWORK. FMC 606.1 |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM. |
| |
| MICHAEL EDWARDS |
| MECHANICAL EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL. 33401 |
| 561-805-6728 |
| [email protected] |
| |