Plan Review Notes
Plan Review Notes For Permit 22091089
Permit Number 22091089
Review Stop B
Sequence Number 1
Notes
Date Text
2022-10-31 13:45:48NEW 2 STORY CHURCH SUNDAY SCHOOL AND OFFICE
 REVIEWED BY ROGER MCPHERSON
 561-805-6716
 [email protected]
 CODE USED FOR REVIEW - 2020 FBC WITH WPB CHAPTER 1
 AMENDMENT
  
 CORRECTIONS NEEDED -
  
 1) PLEASE PROVIDE COMPLETE (FRONT PAGES AND THE
 INSTALLATION INSTRUCTIONS) MIAMI DADE OR FLORIDA STATE
 PRODUCT APPROVALS FOR THE EXTERIOR WINDOWS, DOORS,
 LOUVERS, ROOFING SYSTEMS - ALL PRODUCT APPROVALS NEED
 TO BE REVIEWED AND MARKED APPROVED BY THE BUILDING
 DESIGNER OF RECORD FBC WPB 107.3.4
  
 2) DRAWINGS SHOW BUILDING CONSTRUCTION TYPE AS II B -
 WOOD (TRUSSES, ROOF SHEATHING ETC.) USED IN
 CONSTRUCTION TYPE II BUILDINGS SHOULD BE FIRE RETARDANT
 PER FBC 603.1
  
 3) PLEASE PROVIDE A SITE PLAN - SHOWING THE FOLLOWING
 INFORMATION FBC WPB107.2.5 SITE PLAN. THE CONSTRUCTION
 DOCUMENTS SUBMITTED WITH THE APPLICATION FOR PERMIT
 SHALL BE ACCOMPANIED BY A SITE PLAN SHOWING TO SCALE
 THE SIZE AND LOCATION OF NEW CONSTRUCTION AND EXISTING
 STRUCTURES ON THE SITE, DISTANCES FROM LOT LINES, THE
 ESTABLISHED STREET GRADES AND THE PROPOSED FINISHED
 GRADES, DEPICTING THE PROPOSED LOT DRAINAGE AND, AS
 APPLICABLE, FLOOD HAZARD AREAS, FLOODWAYS, AND DESIGN
 FLOOD ELEVATIONS; AND IT SHALL BE DRAWN IN ACCORDANCE
 WITH AN ACCURATE AND INCLUDED ON A BOUNDARY LINE
 SURVEY. (PLEASE PROVIDE CUT SECTIONS FOR ANY PROPOSED
 WATER RETAINING SWALES)
  
 4) PLEASE PROVIDE A SURVEY.
  
 5) THE REAR RESTROOM WALLS ARE TILED - THE RESTROOM
 WALL FINISH ON THE WALL BESIDE THE TOILETS WILL ALSO
 NEED TO COMPLY WITH FBC 1210.2.2 WALLS AND PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 6) PLEASE SHOW THE WALL FINISH SURROUNDING THE MOP
 SINK/SERVICE SINK TO COMPLY WITH FBC 1210.2.2 WALLS AND
 PARTITIONS.
 WALLS AND PARTITIONS WITHIN 2 FEET (610 MM) OF SERVICE
 SINKS, URINALS AND WATER CLOSETS SHALL HAVE A SMOOTH,
 HARD, NONABSORBENT SURFACE, TO A HEIGHT OF NOT LESS
 THAN 4 FEET (1219 MM) ABOVE THE FLOOR, (DRYWALL IS NOT
 CONSIDERED A HARD SURFACE)
  
 7) A SEPARATE PERMIT IS REQUIRED FOR THE DUMPSTER
 ENCLOSURE AND THE CHILLER.
  
 8) ITEMS SUCH AS BUT NOT LIMITED TO ROOFING SYSTEMS,
 WINDOW AND DOOR PRODUCT APPROVALS ETC. - MAY BE
 DEFERRED SUBMITTALS BY LISTING ITEMS TO BE DEFERRED ON
 THE CONSTRUCTION DOCUMENTS - 107.3.4.1
  
 9) THE SOIL REPORT PROVIDED NEEDS TO BE
 DIGITALLY/ELECTRONICALLY SIGNED TO BE USED IN
 PROJECTDOX (ELECTRONIC PLAN REVIEW).