Plan Review Notes
Plan Review Notes For Permit 22090912
Permit Number 22090912
Review Stop E
Sequence Number 1
Notes
Date Text
2022-11-30 13:24:27ELECTRIC REVIEW FAILED
 1) PLANS DETAIL REPLACING MAIN BREAKER AND ELECTRIC
 PANEL IN ADDITION TO THE PV SYSTEM. PLEASE PROVIDE
 PLANS FOR THE NEW BREAKER AND PANEL INSTALLATION.
 PLEASE INCLUDE THE EXISTING RISER CONDITIONS , NEW
 RISER DIAGRAM, GROUNDING ELECTRODE SYSTEM, PANEL
 SCHEDULES, LOAD CALCULATIONS AND EQUIPMENT AND
 CONDUCTOR SIZES. NEC 215.5 AND FBC 107.2
 2) VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS
 LOW. PROVIDE A BREAKDOWN OF ALL MATERIALS AND LABOR,
 OR, AT YOUR DISCRETION, PROVIDE A SIGNED CONTRACTOR OR
 PROVIDE A REASONABLE VALUE. WPB F.B.C. 109.3
  
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM.
  