Plan Review Notes For Permit 22090900 |
Permit Number |
22090900 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2022-10-13 11:17:34 | 1ST REVIEW FMC | | PERMIT: 22090900 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PLEASE ADD A NOTE ON THE DRAWING EXPLAINING THE RAG | | ON THE WALL AT THE BATHROOM AREA. IS THIS TAKING RETURN | | AIR FROM THE BATHROOM OR IS IT ABOVE THE BATHROOM | | CEILING? FMC 601.5 RETURN AIR OPENINGS. | | 7. RETURN AIR SHALL NOT BE TAKEN FROM A CLOSET, TOILET | | ROOM, KITCHEN, GARAGE, BOILER ROOM, FURNACE ROOM OR | | UNCONDITIONED ATTIC. | | | | 2) PLEASE ADD A NOTE ON THE DRAWING INDICATING HOW THE | | RETURN AIR WILL RETURN BACK TO THE AHU IN THE CLOSET | | LOCATED IN THE CORRIDOR CLOSET. SHOW THE FIRE RATED | | WALLS ON THE DRAWINGS. FBC 107.3.5 | | | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|