2022-10-13 11:17:341ST REVIEW FMC
 PERMIT: 22090900
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE ADD A NOTE ON THE DRAWING EXPLAINING THE RAG
 ON THE WALL AT THE BATHROOM AREA. IS THIS TAKING RETURN
 AIR FROM THE BATHROOM OR IS IT ABOVE THE BATHROOM
 CEILING? FMC 601.5 RETURN AIR OPENINGS.
 7. RETURN AIR SHALL NOT BE TAKEN FROM A CLOSET, TOILET
 ROOM, KITCHEN, GARAGE, BOILER ROOM, FURNACE ROOM OR
 UNCONDITIONED ATTIC.
  
 2) PLEASE ADD A NOTE ON THE DRAWING INDICATING HOW THE
 RETURN AIR WILL RETURN BACK TO THE AHU IN THE CLOSET
 LOCATED IN THE CORRIDOR CLOSET. SHOW THE FIRE RATED
 WALLS ON THE DRAWINGS. FBC 107.3.5
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  