Notes
Date Text
2022-09-30 08:50:47THE VENTILATION CALCULATIONS HAVE CHANGED, THERE IS NO
 VARIABLE OCCUPANCY RULE AT 50 PERCENT IN THE FMC TABLE
 403.3.1.1. PROVIDE THE SQ. FT. OF EACH SPACE ALONG WITH
 THE CALCULATIONS FOR THE SPACES USING FMC TABLE
 403.3.1.1.
  