Plan Review Notes For Permit 22090841 |
Permit Number |
22090841 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2022-10-03 07:54:59 | 2ND REVIEW FBC-2020 PLUMBING | | PERMIT- 22090841 | | 10/3/22 | | | | CODES IN EFFECT: | | FBC P- FLORIDA PLUMBING CODE 7TH EDITION 2020 | | FBC EX- FLORIDA EXISTING BUILDING CODE 7TH EDITION 2020 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. COMMENTS BELOW FROM THE | | 1ST REVIEW WERE NOT ADDRESSED. PLEASE CONTACT ME BY | | PHONE IF YOU NEED FURTHER ASSISTANCE. | | | | 1) THE SUBMITTED SPEC SHEET FOR THE WATTS SERIES 919 | | DOES NOT SHOW THAT THE DEVICE IS LEAD FREE PER THE | | NSF/ANSI 61 STANDARD (0.25% MAX WEIGHTED AVERAGE LEAD | | CONTENT.) | | | | 2) PROVIDE A BASIC SITE PLAN SHOWING THE LOCATION OF | | THE BACKFLOW PREVENTER- SEC. 107.2.1 WPB. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. | | | | CHRISTOPHER L. COLE | | MECHANICAL/PLUMBING PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | |
|