2022-10-03 06:08:47PLEASE ADDRESS PREVIOUS REVIEW COMMENTS BELOW:
  
 THE DOCUMENT SUBMITTED AS GRASS HEAT LOAD IS THE
 MECHANICAL EQUIPMENT SIZING CALCULATIONS. PLEASE SHOW
 THE INSULATION VALUES FOR THE GARAGE AND THAT THEY MEET
 THE FEC IN THE ENERGY CALCULATIONS I HAVE ASKED FOR
 BELOW.
  
  
 1ST REVIEW FMC
 PERMIT: 22090839
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS GARAGE. FEC
 R402
  
 2) PROVIDE A MECHANICAL DRAWING IDENTIFYING THE
 LOCATION OF THE MINI SPLIT HEAD AND THE CONDENSING UNIT
 LOCATION. PLEASE ALSO SHOW THE CONDENSATE DRAIN PIPE
 MATERIAL AND TERMINATION LOCATION. FBC 107.3.5
  
 3) SHOW THE TIE DOWN METHOD USED FOR ANCHORING THE
 CONDENSING UNIT. M1307.2
  
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  