2023-01-27 14:07:551ST REVIEW FMC
 PERMIT: 22090719
  
 CODES IN EFFECT: 2020
  
 FBC- FLORIDA BUILDING CODE
 FMC- FLORIDA MECHANICAL CODE
 FEC- FLORIDA ENERGY CONSERVATION
 FGC- FLORIDA FUEL GAS
 FEX- FLORIDA EXISTING BUILDING CODE
 FRC- FLORIDA RESIDENTIAL BUILDING CODE
 F.S.- FLORIDA STATUTES
 FAC- FLORIDA ACCESSIBILITY CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT.
 FEC R101.5.1.1.1
  
 2) THE OUTDOOR AIR INTAKES WILL NEED TO MEET THE 10
 FEET DISTANCE FROM THE PARKING. FRC 303.5.1
  
 3) THE DRYER EXHAUST DUCTS SHALL BE 4 INCH NOMINAL IN
 DIAMETER AND MINIMUM OF 28 GAUGE THICKNESS. FRC
 M1502.4.1
  
 4) PROVIDE THE TIE DOWN DETAILS FOR THE CONDENSING
 UNITS. FRC M1307.2
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM.
  
 MICHAEL EDWARDS
 MECHANICAL EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL. 33401
 561-805-6728
 [email protected]
  