Plan Review Notes For Permit 22090719 |
Permit Number |
22090719 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2023-01-27 14:07:55 | 1ST REVIEW FMC | | PERMIT: 22090719 | | | | CODES IN EFFECT: 2020 | | | | FBC- FLORIDA BUILDING CODE | | FMC- FLORIDA MECHANICAL CODE | | FEC- FLORIDA ENERGY CONSERVATION | | FGC- FLORIDA FUEL GAS | | FEX- FLORIDA EXISTING BUILDING CODE | | FRC- FLORIDA RESIDENTIAL BUILDING CODE | | F.S.- FLORIDA STATUTES | | FAC- FLORIDA ACCESSIBILITY CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE THE ENERGY CALCULATIONS FOR THIS PROJECT. | | FEC R101.5.1.1.1 | | | | 2) THE OUTDOOR AIR INTAKES WILL NEED TO MEET THE 10 | | FEET DISTANCE FROM THE PARKING. FRC 303.5.1 | | | | 3) THE DRYER EXHAUST DUCTS SHALL BE 4 INCH NOMINAL IN | | DIAMETER AND MINIMUM OF 28 GAUGE THICKNESS. FRC | | M1502.4.1 | | | | 4) PROVIDE THE TIE DOWN DETAILS FOR THE CONDENSING | | UNITS. FRC M1307.2 | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM. | | | | MICHAEL EDWARDS | | MECHANICAL EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL. 33401 | | 561-805-6728 | | [email protected] | | |
|